In The Event Of Fire Or Disconnection - Panasonic Windea VGDT18143W Simple Manual

For apartment building ha d series
Table of Contents

Advertisement

In the Event of Fire or Disconnection

Note
Confirm that system components are properly installed before using the system.
Outbreak of Fire When Using the VGDT Model Base Unit
After approx. 2 minutes
1. Fire detector
2. Fire Confirmation Alarm
(2-stage alarm)
activated alarm
1. Fire Detector Activated Alarm
When the detector detects a fire, the system
reports this detector activation.
The following events occur when the fire
detector activated alarm time (between
approximately 2 to 5 minutes) elapses.
■ 
If the detector remains activated
The alarm changes to the fire confirmation
alarm. (
Page 157)
■ 
If the detector has reset but the alarm is still
sounding
The alarm changes to the fire confirmation
alarm. (
Page 157)
■ 
If the detector has been reset and the alarm
has stopped
Lighting or flashing of devices and screen
displays turn off. (fire reset)
Screen displays can be turned off before
Note
the alarm time has elapsed. (
Page 155)
How to stop the alarm sound
Press the STOP ALARM button on the base
unit.
Pressing the STOP ALARM button on the
call sub-base unit with monitor does not
stop the alarms on other equipment.
Procedures during alarms
Immediately move to the source of the fire
to confirm the current situation. Perform
initial fire extinguishing procedures, report
the fire to the authorities, evacuate the
premises, and perform any other
procedures as appropriate.
Press the FIRE CONFIRM button on the
base unit once you have confirmed the
outbreak of a fire. Inform those in other
condominium units of the fire outbreak.
Cautions
Using gas or kerosene stoves directly
underneath a detector may cause false
detections.
Large amounts of smoke or steam caused
by cooking meat or fish may cause false
detections.
156
The fire detector activated alarm time
Installer
Setting
can be configured to a value between
approximately 2 to 5 minutes in
1-minute increments.
(Default setting: 2 minutes)
Consult with the management
company or the company that
installed the system.
(Siren) The fire detector
has been activated.
Please check.
STOP ALARM button
復旧/警報音停止
FIRE CONFIRM
RESET/ STOP ALARM
button
Appears in red
Appears in white
電源
火災
FIRE
POWER
Call sub-base unit
Door phone
ALARM indicator
Alarm display indicator
FIRE
Flashes in red
Flashes in red
indicator
Alarm is sounding
● For base unit
flashes
in red
非常
EMERG.
警報音停止
STOP ALARM
Appears in red
Appears in white
電源
POWER
● For call sub-base unit with monitor
If a sprinkler detects a fire, the operation as described in section 2
and subsequent sections will be performed immediately.
2. Fire Confirmation alarm
The fire detector activated alarm changes to the fire confirmation alarm in the following
scenarios.
■ 
The detector remains activated after the fire
detector activated alarm time has passed.
■ 
The FIRE CONFIRM button on the base unit
is pressed within the alarm time period.
When the alarm changes to the fire
confirmation alarm, the screen content
and alarm sound also change.
The door phone also sounds an alarm.
The fire icon will turn off after
approximately 3 minutes, and the area
around the MENU button will flash in red.
If the detector is reset from the
integrated control panel or building
receiver in the building manager room,
the alarm stops. Also, the area around
the MENU button, FIRE indicator,
ALARM indicator on the call sub-base
unit, and door phone alarm display
indicator turn off.
The FIRE indicator appears only on the
Note
base unit.
The area around the MENU button, the
FIRE indicator, the ALARM indicator on
the call sub-base unit, and the door
phone alarm display indicator continue to
flash until the detector resets.
The fire icon can also be turned off
within 3 minutes. (
Page 155)
How to stop the alarm sound
Press the STOP ALARM button on the
base unit.
Pressing the STOP ALARM button on
the call sub-base unit with monitor does
not stop the alarms on other equipment.
Note
If the STOP ALARM button on the base
unit is pressed while the fire icon is
displayed on the sub-screen, the
neighborhood fire alarm will sound
(
page 158). In such cases, press the
STOP ALARM button on the base unit
again.
(Siren) Warning, fire, fire.
A fire has broken out. Please
evacuate the premises in a
safe manner. (siren)
STOP ALARM
button
復旧/警報音停止
RESET/ STOP ALARM
Fire icon
flashes
MENU button
in red
Call sub-base unit
ALARM indicator
電源
火災
Flashes in red
FIRE
POWER
Alarm is sounding
FIRE
Door phone
indicator
● For base unit
Alarm display indicator
flashes in red
Flashes in red
Alarm is sounding
警報音停止
STOP ALARM
Fire icon
flashes
in red
MENU button
Appears
in white
電源
POWER
● For call sub-base unit with monitor
157

Advertisement

Table of Contents
loading

Table of Contents