Setting Teamwork Control Parameters - Huawei FusionModule5000 Commissioning Manual

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Commissioning Guide
Parameter
Indoor fan pressure
difference setpoint
Air-side difference pressure
sensor type
Min indoor fan speed
Max indoor fan speed
----End

5.5 Setting Teamwork Control Parameters

Prerequisites
Assign teamwork group number and teamwork unit address for the teamwork controlled
smart cooling products as follows:
Context
The parameters in this section are for reference only. Set actually parameter values as
required.
Procedure
Step 1 On the home screen, tap
shown in
Issue 06 (2020-03-20)
Teamwork group no.: Group the smart cooling products in adjacent areas as one, that is,
assign one teamwork group number for them. At most four teamwork groups can be
assigned (1–4).
Teamwork unit address: The address for the smart cooling product in the same group
cannot be the same (address range: 1–32). The smart cooling product with minimum
address is the master one that collects, processes, and delivers data.
Figure
5-5.
Copyright © Huawei Technologies Co., Ltd.
Description
Sets the value for the
pressure difference control.
Sets the measuring range for
the air side differential
pressure sensor.
Sets the minimum speed for
the indoor fan.
Sets the maximum speed for
the indoor fan.
> Teamwork Settings, to enter Teamwork Settings page, as
5 Commissioning the Cooling System
Configuration Principle
differential pressure sensors
are configured, change to
Pressure diff ctrl.
The default value is 10 Pa.
There is no default value.
Set it to 0–50 Pa.
You are advised not to
change the value.
You are advised not to
change the value.
35