Huawei FusionModule5000 Commissioning Manual page 47

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Commissioning Guide
No.
4
5
6
----End
Follow-up Procedure
After you have completed the settings, perform the following checks to confirm whether the
teamwork control is available:
1.
Issue 06 (2020-03-20)
Parameters
Note
by
Standby: responds to the requirement control when active one is
faulty (critical alarms, shutdown, and offline) or cannot meet
cooling requirements.
M/S
M indicates the master unit, and S indicates a slave unit. Blue
indicates that the device is operating, and gray indicates that the
device is idle.
Frame:
A device with green frame indicates the device itself,
green/non-gr
een
as shown in
A non-green frame indicates the other device in the group,
as shown in
Ground
Red indicates that a critical alarm is generated,
color: red,
bright gray
as shown in
Bright gray indicates that the device is operating without any
critical alarms,
as shown in
If teamwork succeeds, the teamwork icon is green. If teamwork fails, the teamwork icon is red. If
teamwork mode is disabled, the teamwork icon is gray.
Check whether the device number on the topology is the same as the actual device
number.
If yes, go to 2.