Cooling Capacity Management; Setting Cooling Capacity Management Parameters - Huawei FusionModule5000 Commissioning Manual

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Commissioning Guide
Figure 6-41 Viewing IT power information
Step 4 Choose Home > Plan View. In the PUE area, you can view the transient mPUE.
----End

6.6.7 Cooling Capacity Management

6.6.7.1 Setting Cooling Capacity Management Parameters

Prerequisites
Context
Procedure
Step 1 Log in to the ECC800 WebUI as the administrator.
Step 2 Choose Monitoring > Cooling > Running Parameters to access the Temperature and
Humidity Parameters page. Check whether Temperature and humidity control type is
Cold-aisle.
Step 3 Choose Monitoring > Cooling > Running Parameters to access the Running Parameters
page. Set Number of redundant air conditioners and Local yearly highest temperature as
required and tap Submit.
Issue 06 (2020-03-20)
Transient mPUE = Total input power/Total IT power of the smart module. For example, if a
PDU8000 with the total input power of 5 kW connects to the smart module, whose total IT power is
3.6 kW, the transient mPUE = 5 kW/3.6 kW = 1.39.
If the power management is not configured, the PUE area in Plan View displays the average PUE.
All smart cooling products communicate with the ECC800 properly.
The electricity management configuration is complete, and the IT cabinet power
statistics are normal.
The number of smart cooling products (number of started smart cooling products) with
the valid maximum cooling capacity received by the ECC800 is greater than or equal to
the Number of running air conditioners in this group in Teamwork settings of smart
cooling products.
Only for water cooled smart cooling product.
After the smart cooling product is successfully connected to the ECC800, the cooling
capacity management function is enabled by default.
The cooling capacity of the chilled water smart cooling products in the smart module can
be managed by collecting the running parameters of the chilled water smart cooling
products and using the smart module electricity management function.
Copyright © Huawei Technologies Co., Ltd.
6 Commissioning the Management System
101