6.4.2.2 Setting Teamwork Control Parameters

Context
Teamwork control parameters have the following bidirectional coupling relationships:
Number of running units ≤ Total number of units
Procedure
Step 1 Log in to the ECC800 WebUI as admin.
Step 2 Choose Monitoring > Air Conditioner > NetCol5000-A0101 > Running Parameters >
Teamwork Settings to display the page for teamwork setting.
Step 3 Set teamwork control parameters.
Issue 10 (2019-12-20)
Teamwork group no.: Group the smart cooling products in adjacent areas as one, that is,
assign one teamwork control number for them. At most four teamwork control groups
can be assigned (1–4).
Teamwork unit address: The addresses for the smart cooling products in the same group
cannot be the same (address range 1–32). The smart cooling product addressed 1 is the
master one that collects, processes, and delivers data. You are advised to set the value to
an integer in the range of 1 to the number of smart cooling products in the current group.
0101 in NetCol5000-A0101 is variable and subject to change with the smart cooling product connection
sequence. The displayed value prevails.