Step 3 Double-click a network cabinet to access the Basic Configuration page.
Step 4 Check whether the branch information in Apply Power Distribution Standard
Configuration is consistent with the actual situation, and set electricity configuration
parameters such as Device Name, Cabinet height, Power system, Number of power
supplies, and Rated cabinet power as required.
Table 6-28 Basic configuration
Parameter
Device Name
Cabinet height
Power
Distribution
Parameter
Settings
rPDU-A01
rPDU-B01
Branch auto-fill mode
Issue 06 (2020-03-20)
2N non-isolation scenario: The system has only one power distribution cabinet and is
working in dual-power supply mode.
2N isolation scenario: The system has two power distribution cabinets and is working in
single-power supply mode.
For details about the power distribution solution, refer to the power distribution wiring diagram supplied
with the product.
The settings in the following table are used as examples to describe the basic configuration.
Power
system
Number
of power
supplies
Rated
cabinet
power
Copyright © Huawei Technologies Co., Ltd.
Setting
IT Cabinet 101
42
Single-phase
2
6.00
PDU80001 > 1QF1(L1)
PDU80001 > 2QF1(L1)
Ascending order
Descending order
6 Commissioning the Management System
Description
Set based on the actual device
name.
U space quantity of the cabinet.
Set single-phase or three-phase
based on the actual power supply.
rPDU quantity.
Set based on the actual rated
power of the cabinet.
Select a power distribution device
and power distribution branch for
the rPDU numbered rPDU-A01 in
the cabinet.
Select a power distribution device
and power distribution branch for
the rPDU numbered rPDU-B01 in
the cabinet.
If the branch for the first
cabinet is 1QF1(L1),
2QF1(L1), the branches for
subsequent cabinets are
1QF2(L2), 2QF2(L2), and the
like.
If the branch for the first
cabinet is 1QF10(L1),
98