Querying Cooling Capacity Parameters - Huawei FusionModule5000 Commissioning Manual

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Commissioning Guide
Figure 6-42 Setting running parameters
Step 4 Choose Monitoring > Cooling > Running Parameters. In the Cooling Capacity
Management area, set the parameters related to cooling capacity management for the
watercooled smart cooling product, such as the target cooling load factor and recommended
supplywater temperature statistics cycle.
Figure 6-43 Setting cooling capacity management parameters
----End

6.6.7.2 Querying Cooling Capacity Parameters

Prerequisites
The chilled water smart cooling product is successfully connected to the ECC800.
Procedure
Step 1 Log in to the ECC800 WebUI as the administrator.
Step 2 Choose Monitoring > Cooling to access the Running Info page.
Step 3 Query the cooling information about the smart module, such as Cooling capacity for smart
module, Supply water temperature for smart module, Return water temperature for
smart module, and Maximum cooling capacity for smart module, as shown in
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
6 Commissioning the Management System
Figure
6-44.