Huawei FusionModule5000 Commissioning Manual page 40

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Commissioning Guide
Parameter
Control point
temperature
setpoint
Control point
humidity
setpoint
Step 4 Go back to home screen, and tap Running > Device Details > T/H sensor to check that the
cold aisle temperature and humidity are displayed and the values are reasonable.
Issue 06 (2020-03-20)
Description
After the Temperature and humidity
control type and the temperature
value under this type are set, the
device conducts cooling or heating
based on the settings.
After the Temperature and humidity
control type and the humidity value
under this type are set, the device
conducts humidifying or
dehumidifying based on the
settings.
Copyright © Huawei Technologies Co., Ltd.
5 Commissioning the Cooling System
Configuration Principle
the temperature is to be
controlled based on the
minimum data value collected
by the collector.
Set this parameter as required.
Return air temperature: 26–35° C
recommended
Supply air temperature:
18–24° C recommended
Cold aisle temperature: 18–24° C
recommended
Hot aisle temperature: 26–35° C
recommended
Set this parameter as
required.40%–60% RH
recommended
33