Setting Teamwork Control Parameters - Huawei FusionModule800 Installation Manual

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Installation Guide
The following uses 3 cabinet and 1 air conditioner as an example. Three T/H sensors which
addresses are 11, 12 and 21 connect to air conditioner 1 in series, set Cold-aisle sensor 1,
Cold-aisle sensor 2 and Hot-aisle sensor 1 to Enable.
Figure 6-3 T/H sensor layout and DIP switch address (3 cabinet and 1 air conditioner)
----End

6.4.2.2 Setting Teamwork Control Parameters

Context
Teamwork control parameters have the following bidirectional coupling relationships:
Number of running units ≤ Total number of units
Procedure
Step 1 Log in to the ECC800 WebUI as admin.
Step 2 Choose Monitoring > Air Conditioner > NetCol5000-A0104 > Running Parameters >
Teamwork Setting to display the page for teamwork setting.
Issue 02 (2016-11-15)
Teamwork group no.: Group the precision air conditioners in adjacent areas as one, that
is, assign one teamwork control number for them. At most four teamwork control groups
can be assigned (1–4).
Teamwork unit address: The addresses for the air conditioners in the same group cannot
be the same (address range 1–32). The air conditioner addressed 1 is the master one that
collects, processes, and delivers data. You are advised to set the value to an integer in the
range of 1 to the number of air conditioners in the current group.
0104 in NetCol5000-A0104 is variable and subject to change with the air conditioner connection
sequence. The displayed value prevails.