Huawei FusionModule5000 Commissioning Manual page 71

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Commissioning Guide
Context
Linkage Grouping
Table 6-7 Linkage grouping
Linkage Category
Intelligent lighting
a: To link Link smoke alarm with light turn on, Intelligent lighting, and Link fire
control with light turn on, set Monitoring > Aisle > AC Actuator Group > AC
Actuator > Set light mode to Automatic on the WebUI.
Issue 06 (2020-03-20)
The ECC800 can generate an alarm using the multi-functional sensor or smoke sensor in
the aisle. This alarm, however, cannot be used to trigger the customer's fire extinguishing
system.
When detecting fire alarms through the fire controller, the ECC800 opens the skylights
to facilitate fire control, opens the aisle access control system and turns on the lighting to
facilitate escape, and shuts down smart cooling products to prevent the fire from
spreading due to air supply.
An active dry contact signal of the customer's fire extinguishing system cannot be connected to the
ECC800 AI/DI port.
The default status of fire control linkage is off. Set it based on the actual situation.
Shutting down the smart cooling product by fire linkage is used as an example. Refer to
this section for details about opening the skylight, unlocking the aisle access control, and
turning on the lighting system by fire linkage.
In this example, the fire controller connects to port AI/DI_6. The actual port prevails.
Link smoke alarm with
skylight open
Link smoke alarm with
door open
Link smoke alarm with air
conditioner off
Link smoke alarm with
a
light turn on
a
Link fire control with
skylight open
Link fire control with door
open
Link fire control with light
a
turn on
Link fire control with air
conditioner off
Copyright © Huawei Technologies Co., Ltd.
6 Commissioning the Management System
Default
Function
Status
on
If a smoke alarm is raised, the smart
module opens the skylights and access
control by default.
off
If this linkage status is set to on and a
smoke alarm is raised, the smart
cooling products turn off or lights turn
on automatically.
off
If this linkage status is set to on, the
camera detects human motion, and an
infrared alarm is raised, the aisle lights
turn on automatically.
off
If you set this linkage status to on and a
fire occurs in the smart module, the
skylights open, lights turn on, and the
access control opens automatically, or
the smart cooling products turn off
automatically.