FusionModule5000 Smart Modular Data Center
Commissioning Guide
Prerequisites
One end of the straight-through cable has been connected to the RJ45 port on the temperature
sensor, and the other end has been connected to the NTC port on the rack environment unit.
Procedure
Step 1 The temperature sensor supports self-discovery and does not need to set parameters.
Step 2 Check the monitoring functions of temperature sensor.
Table 7-5 Commissioning the sensor
Check Method
Path: Monitoring > Cabinet >
IT Cabinet n > Cabinet
Collector n
----End
7.1.5 How to Set and Add the T/H Sensor (BOM Number:
33010346)
If a T/H sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the RJ45 port on the temperature
sensor, and the other end has been connected to the COM port on the ECC800.
Procedure
Step 1 Set the T/H sensor device address.
1.
Step 2 Add a T/H sensor.
1.
2.
Table 7-6 Adding a T/H sensor
Path
Choose System
Settings >
Device
Management
Issue 06 (2020-03-20)
Go to the LCD screen of the T/H sensor. Press SET to go to the ADD screen, and set the
device address to 1 by pressing + or –.
Log in to the ECC800 WebUI as an administrator.
Add a T/H sensor.
Parameter
Name
Device
attribute
Device Type
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
You can view the current cabinet temperature.
Setting
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list box.