7.1.1 How to Set and Add the Multi-functional Sensor

If a multi-functional sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the POE port on the
multi-functional sensor, and the other end has been connected to the POE port on the ETH
converter.
Procedure
Step 1 Set multi-functional sensor parameters.
On the WebUI, choose Monitoring > Aisle > Multi-Func Sensor Group > Multi-Func
Sensor1 > Running Parameters, ensure that Smoke enable and Temp enable are set to
Enable, set High temperature alarm threshold and other parameters as required, and then
click Submit.
Step 2 Check the functions of the multi-functional sensor.
Table 7-1 Function check
Check Method
Temperature and humidity
detection: View the running
information about the
multi-functional sensor on the
WebUI.
Smoke detection: Simulate a
smoky environment.
Issue 06 (2020-03-20)
If multiple multi-functional sensors are connected, commission one multi-functional sensor first and
then commission the other multi-functional sensors in the same way.