Step 5 Click Finish after checking that electricity has been configured for all IT cabinets, network
cabinets, and smart cooling products.
Step 6 Click Exit Edit Mode to exit the view editing page of the smart module.
Step 7 Choose Monitoring > Cabinet, and set Cabinet load factor overhigh alarm threshold
(default value: 90) on the Running Parameters page. If the default value is used, an alarm
will be raised when the power load factor of the power distribution devices in the smart
module exceeds 90%.
----End

6.6.6.2 Querying Power Parameters

Prerequisites
Power distribution devices are successfully connected to the ECC800.
Procedure
Step 1 Log in to the ECC800 WebUI as the administrator.
Step 2 Query the power usage information about each cabinet, such as the power (kW), power
consumption (kWh), and load factor (%).
Figure 6-40 Power usage information
Step 3 View the IT power information about the smart module.
Issue 06 (2020-03-20)
If Apply to all cabinets is selected, all other cabinets use this configuration.
If Clear the power distribution configuration of all cabinets is selected, the power distribution
configuration of all cabinets will be cleared.
The electricity needs to be configured manually for the devices that are not in the default electricity
configuration range based on the actual situation. Take lighting power supply for example. Choose
Monitoring > Power Distribution > General Input Unit1 > Power Distribution Unit > Running
Parameters > Branch Output Configuration, and set Branch Output Configuration to LED based
on the actual cable connection. Select the branch output configuration and set corresponding parameters
for other power distribution devices based on the actual cable connection.
The alarm hysteresis is 5% by default. That is, if the cabinet load factor overhigh alarm threshold is 90%,
the raised alarm will be cleared when the load factor drops to a value smaller than 85%.