How To Set And Add The Temperature Sensor (Connected To The Ntc Port On The Rack Environment Unit) - Huawei FusionModule5000 Commissioning Manual

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Commissioning Guide
Wire of the Network Cable
Core wire 3 (green-white)
Core wire 6 (green)
Core wire 7 (brown-white)
None (reserved; no connection needed and
to be insulated)
Context
Procedure
Step 1 Set smoke sensor parameters.
1.
2.
3.
Step 2 Check the monitoring functions of smoke sensor.
Table 7-4 Commissioning the sensor
Check Method
Simulate a smoky
environment under
the smoke sensor.
----End
7.1.4 How to Set and Add the Temperature Sensor (Connected to
the NTC Port on the Rack Environment Unit)
If a temperature sensor is installed, perform the following steps to configure it.
Issue 06 (2020-03-20)
If the sensor is prefabricated, only check its settings.
The actual value prevails. Only the method of the parameter settings is described.
In this example, the smoke sensor is connected to the AI/DI_1 port on the skylight actuator.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Aisle > Skylight Actuator Group > Skylight Actuator 1 >
Running Parameters > DI1 alarm level.
Set DI1 alarm level to Low voltage alarm or High voltage alarm, and click Submit.
Set DI1 alarm level to Low voltage alarm if the smoke sensor is connected over NO.
Set DI1 alarm level to High voltage alarm if the smoke sensor is connected over NC.
Normal Connection Status
DI1_smoke alarm is displayed
on the active alarm page of the
app or WebUI.
Copyright © Huawei Technologies Co., Ltd.
Smoke Detector Cable
+12 V (red)
Normally closed end (yellow)
Common end (green)
Normally open end (blue)
Alarm Clearance Method
Press the reset button of the
smoke sensor to clear the alarm.
7 FAQ
108

Advertisement

Table of Contents
loading

Table of Contents