Setting Parameters; Setting The Display Language; Setting Wizard - Huawei PowerCube 1000 Installation Manual

Table of Contents

Advertisement

PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide
Item
Battery voltage
Procedure
Step 1 Check that all DG switches and circuit breakers are OFF.
Step 2 Turn on the power switch for the M48500N1.
Step 3 Manually start the DG. For details, see the DG manual.
Step 4 Check that the DG output voltage is within the normal range using a clamp meter.
Step 5 If the DG works properly, switch the DG AC output circuit breaker to ON.
Step 6 Switch the circuit breaker on the ETP48600-C5B1 to ON.
Step 7 Check that the RUN indicator on the PSU is steady on.
Step 8 Check that the load circuit breaker voltage ranges from –42 V DC to –58 V DC.
----End

12.2 Setting Parameters

12.2.1 Setting the Display Language

After powering on the SMU, press
language. Then press

12.2.2 Setting Wizard

After the Setup Wizard Init screen is displayed, set parameters according to the
following table.
Table 12-2 Setting parameters
Item
Time Zone
Issue 02 (2021-09-28)
Expected Result
The battery voltage is greater than 12 V DC.
Dual–live wire DG: 110 V AC±10%
Three-phase four-wire DG: 230 V AC±10%
NO TE
● If an undesired language is selected, reinstall and restart the SMU and then select the
desired language.
● The preset password for login is 000001.
Settings
Set this parameter to the local time zone.
Copyright © Huawei Technologies Co., Ltd.
or
on the LCD to select a display
to enter the standby screen.
12 Power-on and Commissioning