How To Set And Add The T/H Sensor (Bom Number: 02310Nbs) - Huawei FusionModule5000 Commissioning Manual

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Commissioning Guide
Path
and click Add
Device. The
parameters for
adding devices
are displayed.
3.
Step 3 Check functions of the T/H sensor.
Table 7-7 Function check
Check Method
Check the running information
about the T/H sensor on the
WebUI.
Set T/H sensor alarm thresholds.
----End
7.1.6 How to Set and Add the T/H Sensor (BOM Number:
02310NBS)
If a T/H sensor is installed, perform the following steps to configure it.
Issue 06 (2020-03-20)
Parameter
Name
Connect To
Communicatio
ns Port
Device
Address
Click Test Connect to check whether the T/H sensor connects to the ECC800 properly.
If the T/H sensor connects to the ECC800 properly, click Confirm. The connected
devices are displayed in the Number of connected devices list.
If the T/H sensor does not connect to the ECC800 properly, check whether the cable
between the T/H sensor and the ECC800 is connected properly, whether the T/H
sensor and ECC800 are running properly, and whether the input parameters are
consistent with the T/H sensor parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the T/H sensor is
connected to the COM3 port on the ECC800. If the T/H
sensor is connected to another port, enter the number of the
connected port.
In this example, Device Address is set to 1. During
actual configuration, set the device address for the
T/H sensor based on the actual situation.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group >
T/H Sensor n > Running Info, and check the current
T/H information of the cabinet.
Choose Monitoring > Aisle > T/H Sensor Group >
T/H Sensor n > Running Parameters, and set High
temperature alarm threshold, Low temperature
alarm threshold, High humidity alarm threshold,
and Low humidity alarm threshold as required.
NOTE
The default values of High temperature alarm threshold,
Low temperature alarm threshold, High humidity alarm
threshold, and Low humidity alarm threshold are 30.0° C,
5.0° C, 85.0% RH, and 15.0% RH, respectively.