6.6.6 Power Management

6.6.6.1 Configuring Power Management Parameters

Prerequisites
Context
IT cabinets, network cabinets, and smart cooling products support power management. The
ECC800 connected to an IT cabinet is used as an example in this section.
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose Home > Plan View > Modify Device and click Apply Power Distribution
Standard Configuration to use the default configuration to configure electricity for devices
in the smart module. The following scenarios support the function of applying default
electricity configuration:
Issue 06 (2020-03-20)
Figure 6-38 Creating a user
Set Multi-point logins to a value greater than 2.
In the Assign Device View Rights area, select the cameras to be browsed and queried by
the user. Set other parameters based on the documentation delivered with the equipment
or the documentation obtained by referring to the Preparing Documentation section,
and click Finish.
Power distribution devices (such as the integrated UPS, integrated PDF and precision
PDC) are successfully connected to the ECC800.
The smart module plan view has been created.
N+1 scenario: The system has only one power distribution cabinet and is working in
single-power supply mode.