Huawei FusionModule5000 Commissioning Manual page 73

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Commissioning Guide
Figure 6-11 Modifying a signal name
Step 5 Enable the AI/DI device.
1.
2.
3.
Table 6-8 Fire sensor NO and NC definitions
Item
NO
NC
4.
5.
----End
Follow-up Procedure
After the alarm has been cleared when fire control linkage or smoke alarm linkage occurs,
perform the following operations:
Issue 06 (2020-03-20)
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_6 Port
Settings.
Select Fire sensor to Enable, and click Submit, then enter the AI/DI_6 port settings
page.
Select Fire sensor type and set it to Normal Open or Normal Close as required.
After the corresponding AI/DI device is enabled, the AI/DI device type must be consistent with the DO
state.
Ensure that Fire power supply is set to No.
Click Submit.
Close the skylights manually.
Start the smart cooling products manually.
Copyright © Huawei Technologies Co., Ltd.
6 Commissioning the Management System
Definition
Dry contact signal for the fire sensor
abnormality alarm. Closed: alarm; open:
normal
Dry contact signal for the fire sensor
abnormality alarm. Closed: normal; open:
alarm
66