Huawei FusionModule5000 Commissioning Manual page 118

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Commissioning Guide
Prerequisites
One end of the straight-through cable has been connected to the RS485_IN port on the T/H
sensor, and the other end has been connected to the COM port on the ECC800.
Procedure
Step 1 Set the T/H sensor device address.
Set the T/H sensor device address through the DIP switch on the T/H sensor.
Toggle switches 1 to 6 of the DIP switch specify the device address in binary mode. ON
indicates 1, and OFF indicates 0.
Table 7-8 Setting a device address
Address
1
2
3
4
Step 2 Add a T/H sensor.
1.
2.
Table 7-9 Adding a T/H sensor
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
Issue 06 (2020-03-20)
Toggle
Switch 1
ON
OFF
ON
OFF
Log in to the ECC800 WebUI as an administrator.
Add a T/H sensor.
Parameter
Name
Device
attribute
Device Type
Connect To
Communicatio
ns Port
Device
Address
Copyright © Huawei Technologies Co., Ltd.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
Setting
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the T/H sensor is
connected to the COM3 port on the ECC800. If the T/H
sensor is connected to another port, enter the number of the
connected port.
In this example, Device Address is set to 1. During
actual configuration, set the device address for the
T/H sensor based on the actual situation.
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
7 FAQ
Toggle
Switch 6
OFF
OFF
OFF
OFF
111