Parameter Dual Channel Evaluation Ix & Ix+1; Table 29: Error Detection - WAGO 750-666/000-003 Manual

Wago-i/o-system 750 4fdi/2fdo 24v/10a profisafe v2 ipar, 4-channel digital input and 2-channel digital output module profisafe v2 ipar, 24v/10a semiconductor power output
Hide thumbs Also See for 750-666/000-003:
Table of Contents

Advertisement

104
Commissioning

Table 29: Error detection

Error, example
(x = 1 ... 4, m = 1.2)
Short circuit I1 / I2
Short circuit I3 / I4
Short circuit Ix / +24 V
Short circuit Ix / GND
Short circuit Tm / +24 V
Short circuit Tm / GND
Short circuit T1 / T2
Internal error in input circuit
No supply voltage
Behavior of the PROFIsafe I/O module in the event of a failure
If an error is detected on a digital input or power output by the PROFIsafe I/O
module, the entire PROFIsafe I/O module is passivated by the process image of
all digital inputs being set to "0" and all digital power outputs being switched off.
For detailed information, read the section "Diagnostics".
7.4.5.3
Parameter Dual Channel Evaluation Ix & Ix+1
The Dual channel evaluation parameter is used to switch the dual channel
evaluation of the digital inputs on or off. The value of the parameter can be set to
"yes" or "no". If you have set the value of the operating mode parameter to
"Rotary table, you must set the Dual channel evaluation parameter to "no".
Depending on the value of the Dual channel evaluation parameter, the signal
states of the Ix and Ix+1 inputs are analyzed differently (normal, dual channel),
reproduced in the process image and transferred to the safe PLC.
If you have set the Dual channel evaluation parameter to "no", then the signal
states of the digital inputs are transmitted independently, i.e., single-channel
without analysis to the safe PLC (see Process Image section).
If have you set the Dual channel evaluation parameter to "yes", the respective
digital inputs Ix and Ix+1 are combined into an input pair by the PROFIsafe I/O
module. The signal states of the digital inputs are analyzed based on the rule set
using the Valence evaluation parameter and applied to the process image as 0
signal or 1 signal (see Valence Evaluation Parameter section).
The PROFIsafe I/O module can be used to create two input pairs from the four
digital inputs.
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Short circuit test
"active"
Yes
Yes
Yes
No
Yes*
Yes
Yes*
Yes
Yes
* Only if the clock outputs are connected to
the digital inputs.
Version 1.2.0, valid from HW/SW Version 01/01
WAGO-I/O-SYSTEM 750
Error detection
Short circuit test
"not active"
No
No
No
No
No
Yes
No
Yes
Yes
Manual