Wago I/O Field App; Parameterizing A Module With The Wago I/O Field App; Opc Ua Server - WAGO 765-1205/100-000 Product Manual

8-channel digital input/output; ethercat; 24 v dc; 2.0 a; 8 × m8 connection
Table of Contents

Advertisement

Commissioning
For entering these, there are two checkboxes in the table for each pin of a port: force for
switching the forcing functionality on/off, and set/clr for setting or deleting the setpoint
(1 bit); the latter checkbox is only relevant if the force box is checked. The following ap-
plies to this:
• All inputs for input simulation are entered in the right half of the table under "Input
process data"; all the inputs for output forcing are then entered in the left half of the ta-
ble under "Output process data."
You can find a description of and more information on the forcing function and explana-
tions of terms under
Each of the eight ports (X01 ... X08) has its own table row.
• For pin 4, there is always the option of forcing. Whether forcing is also possible for pin
2 depends on the current configuration of pin 2. Pin 2 must be configured as a digital
input to force the input process data and as a digital output to force the output process
data.
This determines whether or not the pin 2 checkboxes are editable, and Pin 2 or No pin
2 is used as the column title in the screen form.
Concurrent Access
As long as one user is accessing the forcing functionality through a forcing medium, e.g.,
the WAGO I/O Field Webserver, it is locked for all other users of the module. They cannot
access the forcing functionality until the user that is active now terminates his or her ac-
cess.
In this case, the Web browser displays a message box with the text "Somebody else
is already forcing. Try again later." When the forcing functionality is being
accessed, a small orange icon also appears in the forcing option entry in the menu bar on
the left.

10.3.2 WAGO I/O Field app

10.3.2.1 Parameterizing a Module with the WAGO I/O Field App

Note
Read the online help!
You can find Product-specific information on the WAGO App I/O Field in the online help
for the app.

10.3.3 OPC UA Server

The device has an OPC UA server. An OPC UA client can establish a connection with the
device and access the following parameters, among others:
• Device identification
• Configuration parameters
• Process Data
• Measured values
• Diagnostic information
• Statistical information
76
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
8 Forcing
[} 27].
765-1205/100-000

Advertisement

Table of Contents
loading

Table of Contents