NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 335 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P203 – Motor N enns trom @ 0\mod_1327588500455_388.doc x @ 7930 @ @ 1
Nominal motor current
P203
(Nominal motor current)
0.1 ... 1000.0 A
The nominal motor current is a decisive parameter for the current vector control.
{ see information }
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos : 336 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P204 – Motor N enns pannung @ 0\mod_1327588687111_388.doc x @ 7953 @ @ 1
Nominal motor voltage
P204
(Nominal motor voltage)
100 ... 800 V
The >Nominal voltage< matches the mains voltage to the motor voltage. In combination with the
nominal frequency, the voltage/frequency characteristic curve is produced.
{ see information }
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos : 337 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P205 – Motor N ennl eistung @ 0\mod_1327588736705_388.doc x @ 7976 @ @ 1
Nominal motor power
P205
(Nominal motor power)
0.00 ... 250.00 kW
The motor nominal power controls the motor set via P200.
{ see information }
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos : 338 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P206 – Motor c os phi @ 0\mod_1327588784877_388.doc x @ 7999 @ @ 1
Motor cos phi
P206
(Motor cos
0.50 ... 0.95
The motor cos ϕ is a decisive parameter for the current vector control.
{ see information }
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos : 339 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P206 – Motor c os phi_Info_PM SM @ 19\mod_1505894620817_388.doc x @ 2365524 @ @ 1
This parameter is not relevant if a PMSM is used.
Pos : 340 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P207 – Motorsc haltung @ 0\mod_1327589654065_388.doc x @ 8022 @ @ 1
Motor circuit
P207
(Motor circuit)
0 ... 1
0 = star
{ see information }
The motor circuit is decisive for stator resistance measurement (P220) and therefore critical for
current vector control.
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos : 341 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
148
Information
Information
Information
ϕ
)
Information
Information
1 = delta
Information
S
Default setting
S
Default setting
Default setting
S
Default setting
PMSM
S
Default setting
BU 0200 en-3118
P
P
P
P
P