Nord Drivesystems NORDAC FLEX SK 200E Series User Manual page 143

Frequency inverters
Hide thumbs Also See for NORDAC FLEX SK 200E Series:
Table of Contents

Advertisement

Pos : 317 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P100- P199/Parameter P108 – Aussc haltmodus @ 0\mod_1327575421965_388.doc x @ 7665 @ @ 1
Disconnection mode
P108
(Disconnection mode)
This parameter determines the manner in which the output frequency is reduced after "Blocking"
0 ... 13
(controller enable  Low).
{ 1 }
0 = Block voltage: The output signal is switched off immediately. The FI no longer supplies an
1 = Ramp: The current output frequency is reduced in proportion to the remaining deceleration
2 = Ramp with delay: as for 1 "Ramp", however for generational operation the brake ramp is
3 = Immediate DC braking: The FI switches immediately to the preselected DC current (P109).
4 = Const. brake distance, "Constant brake distance": The brake ramp is delayed in starting if
5 = Combined braking, "Combined braking": Dependent on the actual link voltage (UZW), a high
6 = Quadratic ramp: The brake ramp does not follow a linear path, but rather a decreasing
7 = Quad. ramp with delay, "Quadratic ramp with delay": Combination of functions 2 and 6
8 = Quad. comb. braking, "Quadratic combined braking": Combination of functions 5 and 6
9 = Const. acceln. power, "Constant acceleration power": Only applies in field weakening range!
10 = Distance calculator: Constant distance between actual frequency / speed and the set
11 = Const. acceln. power with delay, "Constant acceleration power with delay": Combination of
12 = Const. acceln. power mode 3, "Constant acceleration power mode 3" as for 11, however
13 = Disconnection delay, „"Ramp with disconnection delay": as for 1 "Ramp", however, before
Pos : 318 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
BU 0200 en-3118
output frequency. The motor is only braked by mechanical friction. Switching the FI on again
immediately can lead to an error message.
time, from P103/P105. The DC run-on follows the end of the ramp (→ P559).
extended, or for static operation the output frequency is increased. Under certain conditions,
this function can prevent overload switch off or reduce brake resistance power dissipation.
NOTE:
This function must not be programmed if defined deceleration is required,
e.g. with lifting mechanisms.
This DC current is supplied for the remaining proportion of the >DC brake time< (P110).
Depending on the relationship, actual output frequency to max. frequency (P105), the >Time
DC brake on< is shortened. The time taken for the motor to stop depends on the application.
The time taken to stop depends on the mass inertia of the load and the DC current set
(P109).
With this type of braking, no energy is returned to the FI; heat loss occurs mainly in the
motor rotor.
Not for PMSM motors!
the equipment is not being driven at the maximum output frequency (P105). This results in
an approximately similar braking distance for different frequencies.
NOTE:
This function cannot be used as a positioning function. This function should
not be combined with ramp smoothing (P106).
frequency voltage is switched to the basic frequency (only for linear characteristic curves,
P211 = 0 and P212 = 0). The braking time (P103) is complied with if possible.  Additional
heating in the motor!
Not for PMSM motors!
quadratic one.
Not for PMSM motors!
The drive is accelerated or braked using constant electrical power. The course of the ramps
depends on the load.
minimum output frequency (P104).
functions 2 and 9.
with additional relief of the brake chopper
the brake is applied, the drive unit remains at the absolute minimum frequency set in
parameter (P505) for the time specified in parameter (P110).
Application example: Re-positioning for crane control
5 Parameter
S
P
143

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents