NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Physical structure
Standard
Physical design
Bus length
Structure
Spur cables
Termination resistors
Baud rate
The CAN_H and CAN_L signals must be connected using a
twisted pair of wires. The GND potentials are connected using
the second pair of wires.
Addressing
If several frequency inverters are connected to a system bus, these devices must be assigned with
unique addresses. This should preferably take place via the DIP switch S1 at the device (please see
chapter 4.3.2.2 "DIP switches (S1)").
For field bus modules, no assignment of addresses is necessary. The module identifies all the
frequency inverters automatically. Access to the individual inverters takes place via the field bus
master (PLC) Details of how this is carried out are explained in the relevant bus instructions or data
sheets for the individual modules.
I/O extensions must be assigned to the relevant frequency inverter. This is carried out by means of a
DIP switch on the I/O module. A special case for the I/O extensions is the "Broadcast" mode. In this
mode, the data of the I/O extension (analogue values, inputs etc.) are sent to all inverters
simultaneously. Via the parameterisation in each individual frequency inverter, a decision is made as
to which of the received values are to be used. More information about the settings can be found in
the
Data sheets
for the relevant modules.
Information
Care must be taken that each address is only assigned once. In a CAN-based network double assignment of
addresses may lead to misinterpretation of the data and therefore undefined activities in the system.
Integration of devices from other manufacturers
In principle, the integration of other devices into this bus system is possible. These must support the
CANopen protocol and a 250 kBaud baud rate. The address range (Node ID) 1 to 4 is reserved for
additional CANopen masters. All other participants must be assigned addresses between 50 and 79.
264
CAN
2x2, twisted pair, shielded, stranded wires, wire cross-section ≥0.25 mm² (AWG23),
surge impedance approx. 120 Ω
max. 20 m total expansion (network),
max. 20 m between 2 subscribers,
preferably linear
possible, (max. 6 m)
120 Ω, 250 mW at both ends of a system bus
(with FI or SK xU4-... via DIP switches)
250 kBaud - preset
Addressing