Time boost precontrol
P216
(Time boost precontrol)
0.0 ... 10.0 sec
This parameter is used for 3 functionalities
{ 0.0 }
Time
Only with linear characteristic curve (P211 = 0% and P212 = 0%).
Time limit for suppression of pulse switch-off (P537): enables start-up under heavy load.
Time limit for suppression of switch-off on error in parameter (P401), setting { 05 } "0 - 10V with
switch-off on error 2"
Pos : 355 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P217 – Sc hwi ngungs dämpfung @ 0\mod_1327590520707_388.doc x @ 8255 @ @ 1
Oscillation damping
P217
(Oscillation damping)
0 ... 400 %
With the oscillation damping, idling current harmonics can be damped. Parameter 217 is a measure
of the damping power.
{ 10 }
For oscillation damping the oscillation component is filtered out of the torque current by means of a
high pass filter. This is amplified by P217, inverted and switched to the output frequency.
The limit for the value switched is also proportional to P217. The time constant for the high pass
filter depends on P213. For higher values of P213 the time constant is lower.
With a set value of 10 % for P217, a maximum of ± 0.045 Hz are switched in. At 400 % in P217,
this corresponds to ± 1.8 Hz
The function is not active in "Servo mode, P300".
Pos : 356 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P218 – Modulati onsgrad @ 0\mod_1327590589726_388.doc x @ 8278 @ @ 1
Modulation depth
P218
(Modulation depth)
50 ... 110 %
This setting influences the maximum possible output voltage of the FI in relation to the mains
voltage. Values <100% reduce the voltage to values below that of the mains voltage if this is
{ 100 }e
required for motors. Values >100% increase the output voltage to the motor increased the
harmonics in the current, which may cause swinging in some motors.
Normally, 100% should be set.
Pos : 357 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
BU 0200 en-3118
limit
for
the
boost
lead:
Application
time
5 Parameter
S
P
for
increased
starting
S
P
S
151
current.