Factor I
P533
(Factor I
50 ... 150 %
The motor current for the I
Larger factors permit larger currents.
{ 100 }
Pos : 516 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Parameter P534 – Momentenabschaltgrenz e @ 0\mod_1328093515135_388.doc x @ 11594 @ @ 1
P534
Torque disconn. limit
[-01]
[-02]
(Torque disconnection limit)
0 ... 400 % / 401
Via this parameter both the drive [-01] and the generator [-02] switch-off value can be adjusted.
{ all 401 }
If 80% of the set value is reached, a warning status is set. At 100% switch-off is performed with
an error message.
Error 12.1 is given on exceeding the drive switch-off limit and 12.2on exceeding the generator
switch-off limit.
401 = OFF
Pos : 517 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Parameter P535 – I2t-Motor @ 2\mod_1346932169045_388.doc x @ 43200 @ @ 1
2
I
t Motor
P535
2
(I
t Motor)
0 ... 24
The motor temperature is calculated depending on the output current, the time and the output
frequency (cooling). If the temperature limit value is reached then switch off occurs and error
{ 0 }
message E002 (motor overheating) is output. Possible positive or negative acting ambient
conditions cannot be taken into account here.
The I
different triggering times (<5 s, <10 s and <20 s) can be set. The trigger times are based on
classes 5, 10 and 20 for semiconductor switching devices. The recommended setting for standard
applications is P535=5.
All curves run from 0 Hz to half of the nominal motor frequency (P201). The full nominal current is
available from half of the nominal frequency upwards.
With multi-motor operation the monitoring must be disabled.
0 = I
Switch-off class 5,
60s at 1.5x I
NOTE:
Pos : 518 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
BU 0200 en-3118
2
t-Motor
2
t-Motor)
2
t motor monitoring P535 can be weighted with the parameter P533.
[01] = drive switch-off limit
means that this function has been disabled.
2
t motor function can be set in a differentiated manner. 8 characteristic curves with three
2
t Motor off: Monitoring is inactive
N
I
at 0Hz
P535
N
100%
1
90%
2
80%
3
70%
4
60%
5
50%
6
40%
7
30%
8
Shut-off classes 10 and 20 are provided for applications with heavy starting. When
using these shut-off classes, it must be ensured that the FI has a sufficiently high
overload capacity.
[02] = generator switch-off limit
Switch-off class 10,
120s at 1.5x I
N
I
at 0Hz
P535
N
100%
9
90%
10
80%
11
70%
12
60%
13
50%
14
40%
15
30%
16
5 Parameter
S
S
P
Switch-off class 20,
240s at 1.5x I
N
I
at 0Hz
P535
N
100%
17
90%
18
80%
19
70%
20
60%
21
50%
22
40%
23
30%
24