NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 172.16 /Anl eitungen/Elektroni k/FU und Starter/2. Montage und Installati on/AT EX und EAC EX (SK 1xxE, SK 200E)/SK AT X-POT [SK 1x0E / SK 2xxE] @ 4\mod_1395840390747_388.doc x @ 123211 @ 5 @ 1
SK ATX-POT
The Category 3D frequency inverter can be equipped with an ATEX-compliant 10 kΩ potentiometer
(SK ATX-POT), which can be used to setpoint (e.g. speed) adjustment on the device. The
potentiometer is used with an M20-M25 extension in one of the M25 cable glands. The selected
setpoint can be adjusted with a screwdriver. Due to the detachable screw closing cap, this component
complies with ATEX requirements. Permanent operation may only be carried out with the cap closed.
1
Setting adjustment using a screwdriver
SK ATX-POT
wire colour
red
+10 V reference
black
AGND / 0V
green
Analogue input
Pos : 172.17 /Anl eitungen/Elektroni k/FU und Starter/2. Montage und Installati on/AT EX und EAC EX (SK 1xxE, SK 200E)/INFORM ATION (EX) - Brems wi derstände [SK 1x0E, SK 2xxE] @ 1\mod_1342605607279_388.doc x @ 34178 @ @ 1
Information
If an internal braking resistor of type SK BRI4-x-xxx-xxx is used, the power limitation for this must be activated
under all circumstances  Section 2.3.1 "Internal brake resistor SK BRI4-..."). Only the resistors assigned to the
relevant inverter type may be used.
Pos : 172.18 /Allgemei n/Allgemei ngültige M odul e/---------Seitenumbruch kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
78
Terminal
Name
SK CU4-24V...
[11]
[12]
[14]
Internal braking resistor "SK BRI4-..."
Terminal
Terminal
SK CU4-IOE
[11]
[12]
[12] / [40]
[14] / [16]
[14] / [16]
BU 0200 en-3118