NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 407 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Parameter P350 – PLC F unkti onalität @ 9\mod_1448362540297_388.doc x @ 266297 @ @ 1
PLC functionality
P350
(PLC functionality)
0 ... 1
Activate the integrated PLC
{ 0 }
0 = Off: the PLC is not active, the frequency inverter is actuated in accordance with parameters
1 = To: the PLC is active, frequency inverter is actuated via the PLC, depending on (P351).
Pos : 408 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Parameter P351 – PLC Soll wert Aus wahl @ 9\mod_1448363001241_388.doc x @ 266330 @ @ 1
PLC Setpoint selection
P351
(PLC Setpoint selection)
0 ... 3
Selection of the source for the control word (STW) and the main setpoint (HSW) with active PLC
functionality (P350 = 1). With the settings "0" and "1", the main setpoints are defined via (P553),
{ 0 }
but the definition of the auxiliary setpoints remains unchanged via (P546). This parameter is only
taken over if the frequency inverter is in "Ready to start" status.
0 = STW & HSW = PLC: The PLC supplies the control word (STW) and the main setpoint
1 = STW = P509: The PLC supplies the main setpoint (HSW), the control word (STW)
2 = HSW = P510[1]: The PLC supplies the control word (STW), the source for the main
3 = STW & HSW = P509/510: The source for the control word (STW) and the main setpoint
Pos : 409 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P300- P399/Parameter P353 – Busz ustand über PLC @ 9\mod_1448363834229_388.doc x @ 266393 @ @ 1
Bus status via PLC
P353
(Bus status via PLC)
0 ... 3
This parameter can be used to determine how the control word (STW) for the master function and
the status word (ZSW) of the frequency inverter undergo further processing by the PLC.
{ 0 }
0 = Off: The control word (STW) of the master function (P503≠0) and the status word (ZSW)
1 = STW for broadcast: The control word (STW) for the master value function (P503≠ 0) is set
2 = ZSW for bus: The status word (ZSW) of the frequency inverter is set by the PLC. In order
3 = STW Broadcast&ZSWBus: See setting 1 and 2
Pos : 410 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
162
(P509) and (P510).
The definition of the main setpoints must be carried out accordingly in parameter (P553).
Auxiliary setpoints (P510[-02]) can still be defined via (P546).
(HSW), and parameters (P509) and (P510[-01]) have no effect.
corresponds to the setting in parameter (P509)
setpoint (HSW) corresponds to the setting in parameter (P510[-01])
(HSW) corresponds to the setting in parameter (P509)/(P510[-01])
undergo further processing by the PLC without change.
by the PLC. In order to do this, the control word must be redefined in the PLC using
process value "34_PLC_Busmaster_Control_word".
to do this, the status word must be redefined in the PLC using process value
"28_PLC_status_word".