NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 604 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Parameter P739 – Aktuelle Temperatur Kühl körper [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 2\mod_1346932207653_388.doc x @ 43584 @ @ 1
P739
[-01]
Heat sink temp.
...
(Current heat sink temperature)
[-03]
-40 ... 150°C
[-01] = FI heat sink temperature
[-02] = Internal temperature of the FI
[-03] = Temp. Motor KTY, motor temperature via KTY, recording exclusively via IO extension,
setting in (P400) to function {30} "Motor temperature"
Pos : 605 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Parameter P740 – Pr ozessdaten Bus In [SK 1x0E, SK 2xxE, SK 500...535E, SK 2xxE-FD S] @ 0\mod_1328175248086_388.doc x @ 13313 @ @ 1
P740
[-01]
PZD bus In
...
(Process data Bus In)
[-19]
0000 ... FFFF (hex)
This parameter provides
information
actual control word and
the setpoints that are
transferred via the bus
systems.
For
system must be selected
in P509.
Standardisation:
( section 8.9
"Standardisation
setpoint / target values")
Pos : 606 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
216
[-01 ] = Control word
about
the
[-02] = Setpoint 1 (P510/1, P546)
[-03] = Setpoint 2 (P510/1, ...)
[-04] = Setpoint 3 (P510/1, ...)
display,
a
BUS
[-05] = res.status InBit P480
[-06] = Parameter data In 1
[-07] = Parameter data In 2
of
[-08] = Parameter data In 3
[-09] = Parameter data In 4
[-10] = Parameter data In 5
[-11] = Setpoint 1 (P510/2)
[-12] = Setpoint 2 (P510/2)
[-13] = Setpoint 3 (P510/2)
[-14] = Control word PLC
[-15] = Setpoint 1 PLC
...
[-19] = Setpoint 5 PLC
S
Control word, source from
P509.
Setpoint data from main
setpoint (P510 [-01]).
The displayed value depicts all
Bus In Bit sources linked with
an "OR".
Data during parameter transfer:
Order label (AK), Parameter
number (PNU), Index (IND),
Parameter value (PWE 1/2)
Setpoint data from the master
function value (Broadcast) -
(P502/P503), if P509 = 4
Control word + Setpoint data
from PLC
BU 0200 en-3118