Quick stop time
P426
(Quick stop time)
0 ... 320.00 sec
Setting of the stop time for the fast stop function which can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.
{ 0.10 }
Emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.
Pos : 448 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Parameter P427 – Sc hnell halt bei Störung [SK 2xxE, SK 2xxE-FDS] @ 2\mod_1346931805833_388.doc x @ 42720 @ @ 1
Emergency stop on error
P427
(Emergency stop on error)
0 ... 2
Activation of automatic emergency stop following error
{ 0 }
A quick stop can be triggered by error E2.x, E7.0, E10.x, E12.8, E12.9 and E19.0.
Pos : 449 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Parameter P428 – Automatisc her Anl auf [SK 1x0E, SK 2xxE, SK 2xxE-FD S] @ 2\mod_1346931806519_388.doc x @ 42744 @ @ 1
Automatic start
P428
(
Automatic start)
In the standard setting (P428 =0  Off) the inverter requires a flank to enable (signal change
0 ... 1
from "low high") at the relevant digital input.
{ 0 }
In the setting On  1 the FI reacts to a High level. This function is only possible if the FI is
controlled using the digital inputs. (see P509=0/1)
In certain cases, the FI must start up directly when the mains are switched on. For this P428 = 1
 On can be set. If the enable signal is permanently switched on, or equipped with a cable
jumper, the FI starts up immediately.
NOTE:
NOTE:
NOTE:
Pos : 450 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
BU 0200 en-3118
0 = Disabled: Automatic emergency stop following error is deactivated
1 = Reserved
2 = Activated: Automatic emergency stop following fault
(P428) not "ON" if (P506) = 6, Danger! (See note on (P506))
The "Automatic Start" function can only be used if a digital input of the frequency
inverter (DIN 1 ...) is parameterised to the function "Enable Right" or "Enable Left"
and this input is permanently set to "High". The digital inputs of the technology
modules (e.g.: SK CU4 - IOE) do not support this "Automatic Start" function!
The "Automatic Start" function can only be activated if the frequency inverter has
been parameterised to local control ((P509) setting { 0 } or { 1} ).