10.0
Bus Timeout
E010
10.2
Bus Timeout Option
10.4
Init error Option
10.1
System error option
10.3
10.5
10.6
10.7
10.9
Module missing / P120
Pos : 657 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
BU 0200 en-3118
6 Operating status messages
Telegram time-out / Bus off 24V int. CANbus
Data transfer is faulty. Check P513.
Check physical bus connections
Check bus protocol program process.
Check Bus Master.
Check 24V supply of internal CAN/CANopen Bus.
Node guarding error (internal CANopen)
Bus Off error (internal CANbus)
Telegram timeout
Telegram transfer is faulty.
Check physical bus connections
Check bus protocol program process.
Check Bus Master.
PLC is in the "STOP" or "ERROR" state.
Initialisation error in bus module
Check Bus module current supply.
DIP switch setting of a connected I/O extension
module is incorrect
System error bus module
Further details can be found in the respective
additional bus instructions.
I/O extension:
Incorrect measurement of the input voltage or
undefined provision of the output voltage due to error
in reference voltage generation.
Short circuit at analogue output
The module entered in parameter (P120) is not available.
Check connections