Bus Timeout
E010
10.2
Bus Timeout Option
10.4
Init error Option
10.1
System error option
10.3
10.5
10.6
10.7
10.9
Module missing / P120
Pos : 657 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
BU 0200 en-3118
6 Operating status messages
Telegram time-out / Bus off 24V int. CANbus
•
Data transfer is faulty. Check P513.
•
Check physical bus connections
•
Check bus protocol program process.
•
Check Bus Master.
•
Check 24V supply of internal CAN/CANopen Bus.
•
Node guarding error (internal CANopen)
•
Bus Off error (internal CANbus)
Telegram timeout
•
Telegram transfer is faulty.
•
Check physical bus connections
•
Check bus protocol program process.
•
Check Bus Master.
•
PLC is in the "STOP" or "ERROR" state.
Initialisation error in bus module
•
Check Bus module current supply.
•
DIP switch setting of a connected I/O extension
module is incorrect
System error bus module
•
Further details can be found in the respective
additional bus instructions.
I/O extension:
•
Incorrect measurement of the input voltage or
undefined provision of the output voltage due to error
in reference voltage generation.
•
Short circuit at analogue output
The module entered in parameter (P120) is not available.
•
Check connections