Connection examples
SK CU4-IOE / SK TU4-IOE-...
Connection of a KTY-84 to either of the two analogue inputs of the relevant option is possible. In the
following examples, analogue input 2 of the particular optional module is used.
SK CU4-IOE
Parameter settings (Analogue input 2)
The following parameters must be set for the function of the KTY84-130.
1.
The motor data P201-P207 must be set according to the rating plate.
The motor stator resistance P208 is determined at 20°C with P220 = 1.
2.
Analogue input 2 function, P400 [-04] = 30
3.
(motor temperature)
The mode analogue input 2 P401 [-02] = 1
4.
(negative temperatures are also measured)
(As of firmware version: V1.2)
5.
Adjustment of analogue input 2: P402 [-02] = 1.54 V and P403 [-02] = 2.64 V
(with R
= 2.7 kΩ)
V
Adjust time constants: P161 [-02] = 400ms (Filter time constant is at a maximum)
6.
Parameter (P161) is a module parameter. It cannot be set at the frequency inverter, but must be set directly at the I/O module.
Communication takes place by directly connecting a ParameterBox to the RS232 interface of the module, for example, or by means of
connecting to the frequency converter via the system bus. (Parameter (P1101) object selection → ... )
7.
Motor temperature control (display): P739 [-03]
Pos : 258 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
BU 0200 en-3118
SK TU4-IOE
(Illustration shows a section of the terminal strips)
4 Commissioning
117