Output monitoring
P539
(Output monitoring)
0 ... 3
This protective function monitors the output current at the U-V-W terminals and checks for
plausibility. In cases of error, the error message E016 is output.
{ 0 }
0 = Disabled: Monitoring is not active.
1 = Only motor phases: The output current is measured and checked for symmetry. If an
2 = Only magnetisation: At the moment the FI is switched on, the level of the excitation
3 = Motor phase + Magnet: Monitoring of the motor phases and magnetisation as in 1 and 2
NOTE:
but is not permissible on its own as protection for persons.
Pos : 523 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Parameter P540 – Modus Drehric htung [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 2\mod_1346933274344_388.doc x @ 43752 @ @ 1
Mode phase sequence
P540
(Mode phase sequence)
0 ... 7
For safety reasons this parameter can be used to prevent a rotation direction reversal and
therefore the incorrect rotation direction.
{ 0 }
This function does not operate with active position control (P600 ≠ 0).
*) Applies for control via keyboard and control terminals.
Pos : 524 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
BU 0200 en-3118
imbalance is present, the FI switches off and outputs the error message E016.
current (field current) is checked. If insufficient excitation current is present, the FI switches
off with the error message E016. A motor brake is not released in this phase.
are combined.
This function can be used as an additional protective function for lifting applications,
0 = None, "No restriction of direction of rotation"
1 = Dir key locked, rotation direction change key
2 = Clockwise only*, only clockwise direction is possible. The selection of the "incorrect"
rotation direction leads to the output of the minimum frequency P104 with the field of
rotation R.
3 = Anticlockwise only*, only counter-clockwise direction is possible. The selection of the
"incorrect" rotation direction leads to the output of the minimum frequency P104 with the
field of rotation L.
4 = Enable direction only, rotation direction is only possible according to the enable signal,
otherwise 0Hz.
5 = Clockwise only monitored, "Only clockwise monitored*, only clockwise rotation is
possible. The selection of the "incorrect" rotation direction leads to the FI switching off
(control block). If necessary, a sufficiently large setpoint value (>f
6 = Only anticlockwise monitored, "Only anticlockwise monitored" *, only anticlockwise
rotation is possible. The selection of the "incorrect" rotation direction leads to the FI
switching off (control block). If necessary, an adequately large setpoint value (>f
be observed.
7 = Only enable monitored, "Only enabled direction monitored, Rotation direction is only
possible according to the enable signal, otherwise the FI is switched off.