NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 650 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E005 [SK 180E/SK 2xxE/SK 5xxE/SK2xxE-FD S] @ 2\mod_1347453309234_388.doc x @ 46526 @ @ 1
E005
5.0
Overvoltage UZW
5.1
Mains overvoltage
Pos : 651 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E006 [SK 5xxE, SK 2xxE, SK 2xxE-FD S] @ 2\mod_1361458416246_388.doc x @ 58807 @ @ 1
6.0
Charging error
E006
6.1
Mains undervoltage
Pos : 652 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E007 [SK 135E, SK 200E, SK 500E, SK xxxE-FD S] @ 2\mod_1361460459184_388.doc x @ 58907 @ @ 1
7.0
Mains phase error
E007
Pos : 653 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E008 [SK 2xxE] @ 2\mod_1347453314366_388.doc x @ 46576 @ @ 1
E008
8.0
Parameter loss
(maximum EEPROM value
exceeded)
8.1
Inverter type incorrect
8.2
Reserved
8.3
EEPROM KSE error
(Customer interface incorrectly
identified (customer's interface
equipment))
8.4
Internal EEPROM error
(Database version incorrect)
8.7
EEPR copy not the same
Pos : 654 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E009 "res er viert" [SK 180E/SK 2xxE/SK2xxE-FD S] @ 2\mod_1347453797027_388.doc x @ 46701 @ @ 1
E009
---
Reserved
Pos : 655 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
228
Link circuit voltage too high
Increase deceleration time (P103)
If necessary, set switch-off mode (P108) with delay
(not with lifting equipment)
Extend emergency stop time (P426)
Fluctuating speed (e.g. due to high centrifugal
masses)  adjust U/f characteristic curve if
necessary (P211, P212)
Devices with brake chopper:
Reduce energy return using a braking resistor
Check the function of the connected braking resistor
(broken cable)
Resistance value of connected braking resistor too
high
Mains voltage is too high
See technical data ( Section
Link circuit voltage is too low
Mains voltage too low
See technical data ( Section
Mains voltage too low
See technical data ( Section
Error at terminal connection side
a network phase is not connected
network is non-symmetrical
Error in EEPROM data
Software version of the stored data set not
compatible with the software version of the FI.
NOTE:
Faulty parameters are automatically reloaded
(default data).
EMC interferences (see also E020)
EEPROM faulty
The upgrade level of the frequency inverter was not
correctly identified.
EEPROM with a firmware status of version 1.2 or above
plugged in to an FI with older firmware status → Loss of
parameters! (see also Information in section 5 )
Switch mains voltage off and on again.
7
)
7
)
7
)