NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 678 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/Warnung C 004 [SK 180E ... SK 5xxE] @ 2\mod_1347457006705_388.doc x @ 47224 @ @ 1
4.1
Overcurrent measurement
C004
"Overcurrent measurement"
Pos : 679 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/Warnung C 008 [SK 180E ... SK 5xxE] @ 2\mod_1347457201563_388.doc x @ 47249 @ @ 1
C008
8.0
Parameter loss
Pos : 680 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/Warnung C 012 [SK 180E ... SK 2xxE] @ 2\mod_1347457201968_388.doc x @ 47274 @ @ 1
12.1
Limit moto./Customer
C012
"Drive switch-off limit"
12.2
Limit gen.
"Generator switch-off limit"
12.3
Torque limit
12.4
Current limit
12.5
Load monitor
Pos : 681 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
234
Warning: pulse switch off is active
The limit for activation of pulse switch off (P537) has been
reached (only possible if P112 and P536 are switched off)
FI is overloaded
Drive sluggish, insufficiently sized
Ramps (P102/P103) too steep -> Increase ramp time
Check motor data (P201 ... P209)
Switch off slip compensation (P212)
One of the cyclically saved messages such
Warning:
as operating hours or enabling time could not be
saved successfully.
The warning disappears as soon as saving can be
successfully performed.
Warning: 80 % of the drive switch-off limit (P534 [-01]) has
been exceeded.
Reduce load on motor
Set higher value in (P534 [-01]).
Warning: 80 % of the generator switch-off limit (P534 [-02])
has been reached.
Reduce load on motor
Set higher value in (P534 [-02]).
Warning: 80 % of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12
Warning: 80 % of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14
Warning due to overshooting or undershooting of
permissible load torques ((P525) ... (P529)) for the time set
in (P528).
Adjust load.
Change limit values ((P525) ... (P527)).
Increase delay time (P528).