30 = Set freq before ramp, "Setpoint frequency before frequency ramp", displays the
31 = Output via BUS PZD, the analogue output is controlled via a bus system. The process
33 = Setpoint freq. Motor potentiometer, "Setpoint frequency of motor potentiometer"
60 = Value of PLC, the analogue output is set by the integrated PLC, independently of the
Pos : 443 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Parameter P419 – Nor mi erung Anal ogausgang [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 2\mod_1346931803898_388.doc x @ 42648 @ @ 1
P419
Standard Analogue output
[-01]
[-02]
(Standardisation of analogue output)
-500 ... 500 %
[-01] = First IOE, AOUT of the first I/O extension (SK xU4-IOE)
[-02] = Second IOE, AOUT of the second I/O extension (SK xU4-IOE)
{ all 100 }
only with
Using this parameter an adjustment can be made to the analogue output for the selected
SK CU4-IOE or
operating zone. The maximum analogue output (10 V) corresponds to the standardisation value
of the appropriate selection.
SK TU4-IOE
If therefore, at a constant working point, this parameter is raised from 100 % to 200 %, the
analogue output voltage is halved. 10 Volt output signal then corresponds to twice the nominal
value.
For negative values the logic is reversed. An actual value of 0 % will then produce 10 V at the
output and -100 % will produce 0 V.
Pos : 444 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Parameter P420 – Digitalei ngänge [SK 2xxE] @ 2\mod_1346931804475_388.doc x @ 42672 @ @ 1
P420
[-01]
Digital inputs
...
(Digital inputs)
[-04]
0 ... 80
Up to 4 freely programmable digital inputs are available depending on the version. The functions
can be seen in the following table.
{ [-01]= 1 }
{ [-02] = 2 }
[-01]
{ [-03] = 4 }
[-02]
{ [-04] = 5 }
[-03]
[-04]
When an encoder is being used, digital inputs DIN 2 and DIN 3 must be deactivated using an OR
operation of the parameterised functionality and the encoder evaluation that are always active in
the inverter (parameter P420 [-02, -03]).
The additional digital inputs of the I/O- extensions (SK xU4-IOE) are administered via the
parameter "Bus I/O In Bit (4...7)" - (P480 [-05] ... [-08]) for the first I/O extension, and via the
parameter "Bus I/O In Bit (0...3)" - (P480 [-01] ... [-04]) for the second I/O extension.
Pos : 445 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Parameter P420 – Lis te der möglichen F unkti onen der digital en Ei ngäng e [SK 2xxE] @ 19\mod_1507632085963_388.doc x @ 2367039 @ @ 1
List of possible functions of digital inputs P420
Value
Function
00
No function
01
Enable right
02
Enable left
BU 0200 en-3118
frequency produced by any upstream controllers (ISD, PID, etc.). This is then the target
frequency for the power stage after it has been adjusted via the start-up or braking ramp
(P102, P103).
data is transferred directly (P546 = "32").
current operating status of the FI.
*) Values based on the motor data (P201...), or which are calculated from this.
Digital input 1 (DIN1), Enable right (default), control terminal 21
Digital input 2 (DIN2), Enable left (default), control terminal 22
Digital input 3 (DIN3), Fixed frequency 1 (default), control terminal 23
Digital input 4 (DIN4), Fixed frequency 2 (default), control terminal 24
(DIN4 not with SK 21xE and SK 23xE: Recommended for these devices if "Safe stop" is
used: Parameterise DIN4 to function "10" "Disable voltage" Error message E18.0
suppressed when "Safe stop" triggered)
Description
Input switched off.
The FI delivers an output signal with the rotation field right if a
positive setpoint is present: 0 → 1 Flank (P428 = 0)
The FI delivers an output signal with the rotation field left if a
positive setpoint is present: 0 → 1 Flank (P428 = 0)
5 Parameter
S
P
Signal
---
Hig
h
Hig
h
175