Warning messages
Display in the
SimpleBox / ControlBox
Group
Details in P700
[-02]
Pos : 674 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/Warnung C 001 [SK 180E ... SK 5xxE] @ 2\mod_1347456220101_388.doc x @ 46975 @ @ 1
C001
1.0
Overtemp. Inverter
"Inverter overtemperature"
(inverter heat sink)
Pos : 675 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/Warnung C 002 [SK 180E/SK 2xxE/SK 5xxE/SK2xxE-FD S] @ 2\mod_1347456223954_388.doc x @ 47000 @ @ 1
2.0
Overtemp. Motor PTC
C002
"Overtemperature motor
thermistor "
2.1
Overtemp. Motor I²t
"Motor overtemperature I²t"
Only if I
programmed.
2.2
Overtemp. Brake r.ext
"Overtemperature of external
brake resistor "
Overtemperature via digital
input (P420 [...])={13}
Pos : 676 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/Warnung C 003 [SK 180E ... SK 5xxE] @ 2\mod_1347457006237_388.doc x @ 47199 @ @ 1
3.0
Overcurrent, I
C003
3.1
Overcurrent, chopper I
3.5
Torque current limit
3.6
Current limit
Pos : 677 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
BU 0200 en-3118
Warning
Text in the ParameterBox
2
t motor (P535) is
2
t limit
2
t
6 Operating status messages
Cause
Remedy
Inverter temperature monitoring
Warning: permissible temperature limit reached.
Reduce ambient temperature
Check the FI fan / control cabinet ventilation
Check the FI for dirt
Warning from motor temperature sensor (triggering
threshold reached)
Reduce motor load
Increase motor speed
Use external motor fan
Warning: I2t- motor monitoring (1.3 times the rated current
reached for the time period specified in (P535))
Reduce motor load
Increase motor speed
Warning: Temperature monitor (e.g. brake resistor) has
activated
Digital input is Low
2
Warning: Inverter: I
t limit has triggered, e.g. > 1.3 x I
60s (please also note P504)
Continuous overload at FI output
2
Warning: I
t limit for the brake chopper has triggered, 1.3x
value attained for 60s (also note P554, if present, as well as
P555, P556, P557)
Avoid overload of brake resistance
Warning: Torque current limit reached
Check
(P112)
Warning: Current limit reached
Check
(P536)
for
n
233