I
E003
3.1
Chopper overtemperature I
3.2
IGBT overcurrent
125% monitoring
3.3
IGBT overcurrent fast
150% monitoring
Pos : 648 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E004 [SK 180E/SK 2xxE/SK 5xxE] @ 2\mod_1347453306910_388.doc x @ 46501 @ @ 1
4.0
Overcurrent module
E004
4.1
Overcurrent measurement
"Overcurrent measurement"
Pos : 649 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265495 @ @ 1
BU 0200 en-3118
t overcurrent limit
6 Operating status messages
2
a.c. inverter: I
t limit has triggered, e.g. > 1.5 x I
(also note P504)
Continuous overload at inverter output
Possible encoder fault (resolution, defect,
connection)
2
2
t
Brake chopper: I
t limit has activated, 1.5 times values
reached for 60s (please also pay attention to P554, if
present, and P555, P556, P557)
Avoid overcurrent in brake resistance
De-rating (power reduction)
125% overcurrent for 50ms
Brake chopper current too high
for fan drives: enable flying start circuit (P520)
De-rating (power reduction)
150% overcurrent
Brake chopper current too high
Error signal from module (short duration)
Short-circuit or earthing fault at FI output
Motor cable is too long
Use external output choke
Brake resistor faulty or resistance too low
 Do not shut off P537!
The occurrence of a fault can significantly shorten the
service life of the device, or even destroy it.
P537 (pulse current switch-off) was reached 3x within 50 ms
(only possible if P112 and P536 are disabled)
FI is overloaded
Drive sluggish, insufficiently sized
Ramps (P102/P103) too steep -> Increase ramp time
Check motor data (P201 ... P209)
for 60s