  • Page 1 Quick Start Guide 00825-0100-4851, Rev AH February 2019 ™ Rosemount 3051S High Static Differential Pressure Transmitter...
  • Page 2 Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3051SHP Reference Manual for more information. This document is also available electronically on Emerson.com/Rosemount. Shipping considerations for wireless products. The unit was shipped to you without the power module installed. Remove the power module prior to shipping.
  • Page 3: Table Of Contents

    February 2019 Quick Start Guide Contents System readiness........... 5 Verify configuration........31 Mount the transmitter........7 Trim the transmitter........35 Rotate housing..........14 Safety Instrumented Systems (4-20 mA only).. Set switches and jumpers......16 Product certifications........38 Power up transmitter........18 Quick Start Guide...
  • Page 4 Quick Start Guide February 2019 Rosemount 3051SHP...
  • Page 5: System Readiness

    Rosemount 3051S device revisions and drivers Table 1-1 provides the information necessary to ensure you have the correct device driver and documentation for your device. Table 1-1: Rosemount 3051S Device Revisions and Files Identify device Find device driver Review Review...
  • Page 6 Quick Start Guide February 2019 Table 1-1: Rosemount 3051S Device Revisions and Files (continued) Identify device Find device driver Review Review instructio functiona lity May-07 00809-01 Update 00-4801 Statistical Process Monitorin Capability Sep-06 4, 5, 6 00809-01 00-4801 NAMUR software revision is located on the hardware tag of the device. In accordance with NE53, revisions of the least significant level X (of 1.0.X) do not...
  • Page 7: Mount The Transmitter

    February 2019 Quick Start Guide Mount the transmitter Mount the transmitter in liquid applications Procedure 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so the drain/vent valves are oriented upward. Figure 2-1: Mounting the Transmitter in Liquid Applications Coplanar In-line...
  • Page 8 ™ Emerson provided mounting brackets. Use only bolts provided with the transmitter or sold as Emerson spare parts. Bolts should be tightened to a torque of 125 in-lb. Panel mount Pipe mount...
  • Page 9 February 2019 Quick Start Guide Environmental seal for housing Thread sealing (PFTE) tape or paste on male threads of conduit is required to ® provide a water/dust tight conduit seals and meets requirements of NEMA Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are required.
  • Page 10 Wireless considerations (if applicable) Power up sequence The power module should not be installed on any wireless device until the ™ Emerson Wireless Gateway (Gateway) has been installed and functioning ® properly. See Connect the power module for WirelessHART transmitter more details.
  • Page 11 If the supplied remote mount antenna kit is not installed per these ™ instructions, Emerson is not responsible for wireless performance or non- compliance with spectrum regulations.
  • Page 12 Quick Start Guide February 2019 7. Ensure the mounting mast and lightning arrestor are grounded according to local/national electrical code. Example Figure 2-4: Rosemount 3051S with High Gain, Remote Antenna A. Lightning arrestor B. Antenna C. Mounting mast D. Drip loop...
  • Page 13 February 2019 Quick Start Guide Figure 2-5: Applying Coaxial Sealant to Cable Connections Postrequisites Any spare lengths of coaxial cable should be placed in 1 ft. (0,3 m) coils. Quick Start Guide...
  • Page 14: Rotate Housing

    Quick Start Guide February 2019 Rotate housing To improve field access to wiring or to better view the optional LCD display: Procedure 1. Loosen the housing rotation set screw. 2. Rotate the housing clockwise to the desired location. If the desired location cannot be achieved due to thread limit, rotate the housing counter clockwise to the desired location (up to 360°...
  • Page 15 February 2019 Quick Start Guide Figure 3-2: Transmitter Housing Set Screw (Junction Box) A. Housing rotation set screw (3/32-in.) Quick Start Guide...
  • Page 16: Set Switches And Jumpers

    Quick Start Guide February 2019 Set switches and jumpers If alarm and security adjustment option is not installed, the transmitter will operate normally with the default alarm condition alarm “high” and the security “off”. Procedure 1. Do not remove the transmitter covers in explosive atmospheres when the circuit is live.
  • Page 17 February 2019 Quick Start Guide Figure 4-2: Transmitter Switch and Jumper Configuration (Junction Box) A. Meter/adjustment module B. Security C. Alarm Quick Start Guide...
  • Page 18: Power Up Transmitter

    Quick Start Guide February 2019 Power up transmitter This section provides the steps needed to power up transmitters. These steps are unique based on the specific protocol used. Reference the appropriate section listed below for the specific steps. • Connect wiring and power up for wired HART configuration ™...
  • Page 19: Quick Start Guide

    February 2019 Quick Start Guide minimum of seven threads must be engaged. For tapered threads, a minimum of five threads must be engaged. 6. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
  • Page 20: Quick Start Guide

    Quick Start Guide February 2019 Figure 5-3: With Optional Process Temperature Connection A. RL ≥ 250 Ω B. Power supply Note Installation of the transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded. Signal wiring grounding Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment.
  • Page 21: Quick Start Guide

    Remote display wiring and power up (if applicable) The remote mount display and Interface system consists of a local transmitter and a remote mount LCD display assembly. The local Rosemount 3051S assembly includes a Junction Box housing with a three-position terminal block integrally mounted to a sensor module.
  • Page 22: Quick Start Guide

    Madison AWM Style 2549 cable. Alternate cable may be used as long as the transmitter with remote display and cable is configured according to the installation control drawing or certificate. Refer to appropriate approval certificate or control drawing in Appendix B of the Rosemount 3051S Reference Manual for remote cable IS requirements.
  • Page 23: Quick Start Guide

    Quick connect wiring (if applicable) As standard, the Rosemount 3051S Quick Connect arrives properly assembled to the sensor module and is ready for installation. Cordsets and field wireable connectors (in shaded area) are sold separately.
  • Page 24: Quick Start Guide

    Quick Start Guide February 2019 Figure 5-6: Rosemount 3051S Quick Connect Exploded View A. Straight field wireable connector (part number 03151-9063-0001), supplied by customer B. Right angle field wireable connector (part number 03151-9063-0002), supplied by customer C. Quick Connect housing D.
  • Page 25: Quick Start Guide

    February 2019 Quick Start Guide Figure 5-7: Quick Connect Housing Pin-Out “+” “ ” A. Ground B. No connection Note For other wiring details, refer to pin-out drawing and the cordset manufacturer’s installation instructions. Power supply The DC power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces.
  • Page 26: Quick Start Guide

    Quick Start Guide February 2019 Figure 5-9: Load Limitation (HART Diagnostic Transmitter [Option Code DA2] Differential Pressure and Temperature Transmitter) 1322 1000 Operating region 12.0 42.4 Voltage (Vdc) Maximum Loop Resistance = 43.5 x (Power Supply Voltage – 12.0) Install optional process temperature input (Pt 100 RTD sensor) Use only ATEX/IECEx Flameproof cables (Temperature Input Code C30, C32, C33, or C34) to meet ATEX/IECEx Flameproof certification.
  • Page 27 February 2019 Quick Start Guide Figure 5-10: Transmitter RTD Wiring Connection A. Pt 100 RTD sensor B. RTD cable assembly wires C. Ground lug ™ Connect wiring and power up F Fieldbus OUNDATION transmitter Cable connection The segment cable can enter the transmitter through either conduit connection on the housing.
  • Page 28: Quick Start Guide

    Quick Start Guide February 2019 Signal termination Every fieldbus segment requires terminators at each end of the segment. Failure to properly terminate segments may cause communication errors with devices on the segment. Transient protection Transient protection devices require the transmitter be grounded for proper operation.
  • Page 29: Quick Start Guide

    Gateway, beginning with the closest. This will result in a simpler and faster network installation. Enable active advertising on the Gateway to ensure new devices join the network faster. For more information, see the Emerson 1420 Wireless Gateway Reference Manual. Quick Start Guide...
  • Page 30: Quick Start Guide

    Quick Start Guide February 2019 Procedure 1. Remove the housing cover on the field terminal side. 2. Connect the black power module. Figure 5-12: Power module for WirelessHART transmitter connections Rosemount 3051SHP...
  • Page 31: Verify Configuration

    (LCD); verification can also be done at the device via the LCD display. Table 6-1: Device Revisions Device configuration Device revision ™ Rosemount 3051S HART (wired) Rev. 7 ™ Rosemount 3051S F Fieldbus Rev. 23 OUNDATION Rosemount 3051S WirelessHART Rev. 3 ™ Rosemount 3051S MultiVariable Rev. 1 ®...
  • Page 32 Quick Start Guide February 2019 Field Communicator connections ® Figure 6-1: WirelessHART terminal block P/N 00753-9200-0010 COMM ® Figure 6-2: HART and DA2 terminal block Figure 6-3: Multivariable terminal block Rosemount 3051SHP...
  • Page 33 Manual. Verify WirelessHART operation using the Local display (LCD) The LCD display will show the output values based on the wireless update rate. Refer to the Rosemount 3051S Wireless Reference Manual for error codes and other LCD display messages. Press and hold the Diagnostic button...
  • Page 34 It may take several minutes for the device to join the network. For advanced troubleshooting of the wireless network or Gateway, see the Rosemount ™ 3051S WirelessHART Reference Manual, Emerson 1410 Wireless Gateway Reference Manual, Emerson 1420 Wireless Gateway Reference Manual Quick Start Guide. Rosemount 3051SHP...
  • Page 35: Trim The Transmitter

    February 2019 Quick Start Guide Trim the transmitter Transmitters are shipped fully calibrated per request or by the factory default of full scale (lower range value = zero, upper range value = upper range limit). Zero trim A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects.
  • Page 36 Quick Start Guide February 2019 Figure 7-2: Transmitter Adjustment Buttons (Junction Box) A. Zero B. Span Rosemount 3051SHP...
  • Page 37: Safety Instrumented Systems (4-20 Ma Only)

    February 2019 Quick Start Guide Safety Instrumented Systems (4-20 mA only) For safety certified installations, refer to the appropriate manual for installation procedure and system requirements. Quick Start Guide...
  • Page 38: Product Certifications

    A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Installing Equipment in North America ®...
  • Page 39 February 2019 Quick Start Guide IE US FISCO Intrinsically Safe Certificate 1143113 Standards FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3810 - 2005, UL 50E 1st Ed., UL 61010-1 (3rd Edition) Markings IS CL I, DIV 1, GP A, B, C, D, T4(-50 °C ≤ T ≤...
  • Page 40 Quick Start Guide February 2019 Europe E1 ATEX Flameproof Certificate DEKRA 15ATEX0108X Standards EN 60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-26:2015 Markings II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6 (–60 °C ≤ T ≤ +70 °C), T4/T5 (–60 °C ≤ T ≤...
  • Page 41 IP20 in accordance with IEC/EN 60529. 3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
  • Page 42 IP20 in accordance with IEC/EN 60529. 3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
  • Page 43 February 2019 Quick Start Guide 4. The SuperModule(s) must be securely screwed in place to maintain the ingress protection of the enclosure(s). N1 ATEX Type n Certificate BAS01ATEX3304X Standards EN 60079-0:2012, EN 60079-15:2010 Markings II 3 G Ex nA IIC T5 Gc, (–40 °C ≤ T ≤...
  • Page 44 7. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7 J impact test. 8. The Rosemount 3051S SuperModule must be securely screwed in place to maintain the ingress protection of the enclosure. I7 IECEx Intrinsic Safety Certificate IECEx BAS 04.0017X...
  • Page 45 IP20 in accordance with IEC/EN 60529. 3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
  • Page 46 IP20 in accordance with IEC/EN 60529. 3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
  • Page 47 February 2019 Quick Start Guide K7 Combination of E7, I7, and N7 KC Combination of E1, E5, I1, and I5 KD Combination of E1, E5, E6, I1, I5, and I6 KG Combination of IA, IE, IF, and IG KM Combination of EM and IM Quick Start Guide...
  • Page 48 Quick Start Guide February 2019 Rosemount 3051SHP Declaration of Conformity EU Declaration of Conformity No: RMD 1104 Rev. F Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 declare under our sole responsibility that the product, Rosemount™ 3051SHP Pressure Transmitter manufactured by, Rosemount Inc.
  • Page 49 February 2019 Quick Start Guide EU Declaration of Conformity No: RMD 1104 Rev. F EMC Directive (2014/30/EU) Harmonized Standards: EN 61326-1:2013, EN61326-2-3: 2013 Radio Equipment Directive (RED) (2014/53/EU) Harmonized Standards: EN 300 328 V2.1.1 EN 301 489-1 V2.2.0 EN 301 489-17 V3.2.0 EN 61010-1: 2010 EN 62479: 2010 PED Directive (2014/68/EU)
  • Page 50 Quick Start Guide February 2019 EU Declaration of Conformity No: RMD 1104 Rev. F BAS01ATEX3304X – Type n Certificate Equipment Group II, Category 3 G Ex nA IIC T5 Gc Harmonized Standards Used: EN 60079-0:2012+A11:2013, EN 60079-15:2010 BAS01ATEX1374X – Dust Certificate Equipment Group II, Category 1 D Ex ta IIIC T105°C T 95°C Da...
  • Page 51 February 2019 Quick Start Guide EU Declaration of Conformity No: RMD 1104 Rev. F ATEX Notified Bodies for Quality Assurance SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland Page 4 of 4 Quick Start Guide...
  • Page 52 Quick Start Guide February 2019 China RoHS Rosemount 3051SHP China RoHS List of Rosemount 3051SHP Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6) (PBB) (PBDE)
  • Page 53 February 2019 Quick Start Guide Quick Start Guide...
  • Page 54 Quick Start Guide February 2019 Rosemount 3051SHP...
  • Page 55 February 2019 Quick Start Guide Quick Start Guide...
  • Page 56 The Emerson logo is a Facebook.com/Rosemount trademark and service mark of Emerson Electric Youtube.com/user/ Co. Rosemount is mark of one of the Emerson RosemountMeasurement family of companies. All other marks are the Google.com/+RosemountMeasurement property of their respective owners.