Commissioning instructions
IO domain bridge network switch settings
Control panel
IO Card
all switches to
Off position
Network Card
Address 2
Baud 38.4K
DKC
Address 1
Baud 19.2K
Node 2
Node 1
Node 3
Control panel
Network Card
Address 3
Baud 38.4K
IO Card
all switches to
Off position
IO Card switches must be set to Off,
DKC
these are now located on the DKC.
Address 1
Baud 19.2K
94
Switch settings on cards inside
EN54 Vigilon panels / Nodes
where Domain Bridge IO Card
is used to network the fire systems
Domain 1
Control panel
Domain Bridge
Network card address setting is for the
Domain Bridge IO Card address setting is for the
Baud rate settings must be set as shown in this diagram.
Domain 2
Control panel
Node address
Domain address
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Control panel
IO Card
all switches to
Off position
Network Card
Address 2
Baud 38.4K
DKC
Address 2
Baud 19.2K
Node 2
Node 1
Node 3
Control panel
Network Card
Address 3
Baud 38.4K
IO Card
all switches to
Off position
DKC
Address 2
Baud 19.2K