Command Builds - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions

Command Builds

COMMAND
ACTION (INPUT)
BUILD
MASTER
SECTOR
CHANNEL
Integral
sounder
TRIGGER
TIME
BLOCK
TRIGGER
TRIGGER
I / O INTERFACE
INPUT LINE
TRIGGER
SECTOR
TRIGGER
That has just
come into fire
'LABEL' OR NUMBER
ASSIGN
Sound
Sound
ASSIGN
Silence
ASSIGN
Reset
TRIGGER
NONE
(CLEAR)
TRIGGER
ZONE
DIFFERENT
TASK
MENU
FROM ANOTHER ZONE
NOTE: NORMALLY THE
BUILD REVERSE ACTIONS
IS SELECTED.
"
Where possible use sectored action instead of command build action.
¨
There can be up to 255 Command builds per panel
¨
a Command build can only be set up with one trigger (can be a range)
¨
a Command build can be triggered:
for reversible action (automatic deaction on removal of trigger)
152
COMMAND BUILD FUNCTIONS
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
ACTIONS
REV OR NOT-REV
1 TO 255
COMMAND
REV OR NOT-REV
BUILD
REV OR NOT-REV
REV OR NOT-REV
UP TO 40 CHARACTERS
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
or non-reversible action, (deactioned by another Command
build for a non-fire trigger or reset for a fire trigger).
NOT-REVERSIBLE
¨
the Command build trigger for Zone tasks reside under the zone
REVERSIBLE
menu/function
¨
Command builds that are triggered through a Sector fire event
START MASTER ALARM
will deaction on fire reset. This is independent of whether the
STOP MASTER ALARMS
1ST
NO ACTION (CLEAR)
Sector is configured to deaction on silence alarms
ENABLE
¨
DISABLE
Command builds that are configured for turn Off actions have
PRINTER
no reverse action to turn On again, another Command build or
SECTOR
manual action is required
MASTER SECTOR
¨
FARE
Command builds can be used under fire and non fire conditions
SOUNDER
(INTEGRAL
to carry out pre-configured actions built up from the Control
SOUNDER IN
SENSOR/ALARM
DEVICE
menu command
AUX RELAY
¨
a Command build can only be set up to perform one action (can
TIMESLOT
2ND
OVERRIDE
be a range), any split range would require a second Command
DELAY - TO 24 HR
build
DELAY BLOCK
PAUSE SOUNDERS
¨
DELAY 0 TO 30 SEC
each Command build can be given a 40 character label to be
LOCAL BUILD
displayed and/or printed when triggered. If no label is given
SOUND
then nothing will be displayed
SILENCE
¨
if a label is given, the local buzzer will operate for 1 minute
RESET
VERIFY
when the Command build is active
DIGITAL
¨
Command builds are logged with an On/Off time, this
information can be viewed by selecting [info] -> <etc> ->
BACKGROUND
[Event]-> <etc> -> [Supervis]-> [Log] -> [Enter] and if still
MUSIC
EMERGENCY
On via [Info]-> [Event]-> <etc> -> [Supervis]-> [Active] ->
MESSAGE
[Enter], this is only possible if a label has been given to the
AUX MESSAGE
EMERGENCY MIC
Command Build
PLAY MESSAGE
¨
when speed of operation is required the lowest number
PA
D1 VOICE
Command builds should be used as these are processed first
FARE
¨
if a digital output line is to be actioned by a Command build,
the I/O line should not be assigned to a Sector as it may
deaction when the silence alarms is pressed regardless of the
Command build still being active
¨
a fire condition takes priority over a Command build
&
input line, as this will effectively disable the input.
Take great care not to action a digital output to an