Commissioning instructions

Checking a loop map

A loop map is checked against the as fitted wiring drawings. This will confirm the exact location of
each system device and its address.
It is possible to display or print a loop map.
¨
Press the Menu On/Off button and then [Info] -> [Display]/[Print], note print will
only appear if a printer is connected to the panel. Momentarily press <etc> to select
[Loop Map] (note the menu is different if a network card is fitted in the panel as
there will be a [Net Map] option), type in a loop number and select [Enter]. The loop
map is either displayed or printed, a typical example is shown below.
Map information for Loop 2
Os Prev Next
Common
1
End1
2
2
1
3
3
2
4
4
3
9
L2
5
4
6
6
5
7
7
6
8
Address of next device
Address of previous device
Address of the device
58
15:45
Position
Main Loop
Main Loop
Main Loop
5
Spur Loop
Spur Loop
Spur Loop
Spur Loop
Spur Loop
Where the device is
located, either on the
main or spur loop

To find devices on a loop circuit

Checking physical location of devices on a loop map is made easier by having two people in
communication with each other. While one person walks around the site and mark off the devices
on the as fitted wiring drawings, the other person operates the panel controls.
The 'find' device is a function that gives visual or audible indication at the respective device on a
loop circuit. The following procedure assumes no password access is required.
¨
Press the Menu On/Off button and then [Test/Eng] -> [Usercode] ->[Loop] ->[Find
Dev], now enter CARD number n of loop circuit n, select [Start] and type in a device
number (usually device 1 if starting from the beginning) and then select [Enter]. The
display shows the device and loop number:
Number 1 on Loop 1
¨
Press [Next] to find the next device on the loop and at any stage if the previous device
needs to be found then select [Previous].
A found device will provide visual or audible indication.
S-Quad Sensors and MCP
¨
A fire sensor or system manual call point will operate its LED for 0.5 second On and
0.5 second Off repeated.
Sounders and S-Cubed
¨
Each system alarm sounder on S cubed or S-Quad device will provide an audible and
/ or visual indication for 0.5 second On and 0.5 second Off repeated.
Mains powered DAU and micro DAU
¨
A Mains powered DAU will switch On an LED located on the main board, which
changes from blink to 1s on 1s off when it is found.
Interface units
Ensure the outputs are not connected to external equipment at this stage of
commissioning.
¨
Each interface output will in turn be activated for 0.5 second On and 0.5 second Off,
this process will repeat.
Panels on loop circuits
¨
A mimic and repeat panel on a loop circuit will display its device number.