Commissioning instructions

Setting the DKC card

The links, pot and switch on the DKC are factory configured as shown below.
DKC ASSEMBLY
Danger
WARNING
REMOVAL OF COVER
EXPOSES HIGH V
H VOLTAGES
Inner door assembly
SW1
OFF
Link is NOT USED
leave link fitted.
It is for special use
with keyswitch
application
Control buttons
Sound Alarms
Factory setting
is with link fitted
Buttons
Verify
enabled
Reset
Buttons
Silence Alarms
disabled
26
LCD Contrast adjust
Anti-Clockwise -
Lighter
RV1
Clockwise -
Darker
RV1
Display and
keyboard Card (DKC)
8
7
6
Inner door
5
4
3
2
1
ON
With Zone
indicators
(EN)
1
2
3
Zones
17
18
19
Without Zone
indicators
(BS) panel or
Network node
Control buttons
"
The emergency control buttons must always be left in an enabled state, with the 'control
buttons' link fitted.
There is no indication given at the panel when the link is set for inactive controls.
Display Contrast
¨
The display contrast is set using the Pot RV1 on the DAC, which is factory adjusted
for optimum contrast. You can also adjust the contrast using the menu option under
[Test/Eng], see Appendix A menu maps.
"
The contrast adjustment function using the menu options may not be
applicable for some older build of panels.
P1
Domain Address and baud rate settings
Typically the Baud rate set using these switches should be the same as the setting made using the
P6
[TestEng] menu. The baud rate set must be backed up to the NVM. Where a baud rate value that
can only be achieved by [Test/Eng] menu, this must be set using the menu and backed up to NVM.
Baud Rate
Domain address
2
Baud 3
1
Off
Off
1200
Off
Off
On
2400
Off
On
Off
9600
Off
On
On
19200
On
On
4
20
Factory set domain address - 1 with 19200 baud (see SHADED cells)
Zone indicators
The Zone indicators are enabled for normal operation at an EN control panel and must NOT be
disabled.
The zone indicators are not applicable on a Network node nor on a BS Control panel. On these
products the 'zone indicator' links are set in the 'disable' position.
5
6
7
8
4
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
Off
On
Off
etc
On
On
On
On
Off
On
On
On
On
On
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Address
64
1
2
62
63