Id²Net Network Module - Honeywell Notifier INSPIRE E10 Installation Instructions Manual

Fire alarm control panels
Hide thumbs Also See for Notifier INSPIRE E10:
Table of Contents

Advertisement

Panel Installation
ID²NET NETWORK MODULE
1 -
2 -
3 -
4 RS485 #B Pin B
5 RS485 #B Pin A
1 2 3 4 5
6 7 8 9 10
6 -
7 -
8 -
9 RS485 #A Pin B
10 RS485 #A Pin A
ID2NET NETWORK
The ID²Net Network Module (HOP-631-100)
provides the isolated RS485 ports for a copper
network of INSPIRE panels. The module has
provision for conversion to Optical Fibre using plug-
in adaptors. Any combination of RS485 and Optical
Fibre is possible.
ID²NET Network module is colour coded Yellow
Dimensions H-130 mm x W-28 mm x D-117 mm
Copper connection to terminal blocks
Two isolated RS-485 ports are available as
standard
56
NET
ID2NET
Yellow
Optional plug-in adapters to convert to Optical Fibre
Any combination of RS-485 / Optical Fibre allowed
Module can be given a 40 character software label for
display on panel HMI
COPPER NETWORK CABLE
See approved lists of cables used for the wiring of
ID2NET Copper Network loop.
MULTI MODE FIBRE NETWORK CABLE
See approved list of fibre cable used for the wiring of
ID2NET Fibre Network loop.
INDICATORS
Green LED
Lit - Power On, Unlit - Power Off
Blinking - when registration, Initialisation or upgrade
process is active.
Yellow LED
Lit - Common fault at module, Unlit - No fault

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier inspire e15