Commissioning instructions
S-Quad Dual Optical, Heat & CO sensor STATES
State
Definition / Class
State 1
High sensitivity optical, Class A1 heat,
high sensitivity gas
State 4
Medium sensitivity optical with spike
protection, Class A1 heat, medium
sensitivity gas
State 0# Medium sensitivity optical,
Class A1 heat, medium sensitivity gas
State 2
Medium sensitivity optical,
Class A1 heat, low sensitivity gas
State 9
Medium sensitivity gas,
Class A1 heat
State 11 Medium sensitivity optical,
Class B heat
State 12 Class A1 heat only
State 15 No detection

S-Quad Optical sensor STATES

# - factory default STATE
State
Definition / Class
State 3
High sensitivity optical
State 4
Medium sensitivity with no spike
protection
State 0# Medium sensitivity optical
State 8
Delayed medium sensitivity optical
State 2
Low sensitivity optical
State 15 No detection
76
Application in / Suitable for:
Clean area or environment where early detection is required with false alarm reduction
General area as State 0 with less immunity to steam and dust for ease of testing using artificial
smoke in normal operating mode, when test / commissioning mode is not active
General area where false alarm reduction is required for comprehensive fire detection
Applications with moderate dust, smoke (tobacco) or steam
Area where high levels of smoke, dust or steam is often present
Area with high ambient temperature, plus low levels of dust, smoke or steam present
Area where smoke, dust, steam or gas occurs at times
Application in / Suitable for:
Clean area or environment, where early detection is required
General area as State 0 with less immunity to steam and dust to facilitate wittiness test
General area
General area with transient steam, dust or smoke present
Area with moderate dust, smoke or steam present
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Sensitivity
a-high- to-h-none
a
b
c
d
e
f
g
h
Sensitivity
a-high- to-f-none
a
b
c
d
e
f

Advertisement