Single Vigilon Network

A VIGILON network consists of a number of control panels of standalone systems and network
nodes wired together in a secure loop using copper or fibre network cards.
A secure loop is achieved by installation of a copper or fibre network cards in each VIGILON panel
and VIGILON Network Node to facilitate the interconnection of panels and nodes. Each standalone
system is first commissioned before being networked together with other panels and nodes.
The commissioning involves systematic introduction of each standalone system to the network and
tests to ensure the network is working.
The whole networked system is then configured and tested to ensure alarms and global controls
operates to site requirements.
"
When setting the address switches on the 'network card', ensure the network controller
is given the lowest address.
A network controller is a node/panel that can be connected to a Central monitoring
system.
All panels in a networked system must operate at the same baud rate, normally this value
is 38.4K where copper network cards are being used and 115.2K where Fibre network
cards are being used.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes

Single Network

¨
Each standalone system must first be fully commissioned individually.
¨
Check that the correct cable is used to wire the network.
side 1
Network card (NC) *
Loop processor card (LPC) x 6
Input output card (IOC)
Local controller card (LCC)
Control panel
RS485 - up to 1.2Km
Fibre optics - up to 2Km
side 2
Secure
Network
side 1
side 2
Network card (NC) *
RS485 - up to 1.2Km
Spare
Fibre optics - up to 2Km
Input output card (IOC)
Local controller card (LCC)
Network Node
side 2
RS485 - up to 1.2Km
Fibre optics - up to 2Km
Central Monitoring
system
RS232
15m
max
side 1
* - can be copper or fibre network card
side 2
RS485 - up to 1.2Km
Fibre optics - up to 2Km
side 1