S-Cubed Mark 2 (Legacy Product Range) - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions
LPCB approved S-Quad Sensor STATES (Legacy product range)
Device
Dual Optical & Heat sensor variant -
(With Speech)
(With Strobe & Speech)
(With Sounder)
Dual Optical, Heat & CO sensor variant -
(With Speech & Strobe)
Optical & Heat sensor variant -
(With Sounder)
Heat sensor variant -
(With Speech & Strobe)
(With Sounder)
All S-Quad range of sensor sounder devices meet CEA 4021: 2003-07, where applicable, and meet EN54-17:2005 Input/Output devices plus EN54-18:2005 Short circuit isolation for use on the
transmission path of fire detection and alarm systems.
Sounder tone - Meets the following tone settings: High tone ( Continuous 933Hz) & Alternate tone (High 933Hz for 0.25s / low 700Hz for 0.25s)
When an S-Quad sensor is configured to operate a non LPCB approved STATE then this will contravene the LPCB approval.
# - these standards are met when the sensor is operating LPCB approved STATES.
All the LPCB approved STATES applicable to S-Quad fire sensors are shown. The required STATE is configured during commissioning. On initial power-up of the
system all the sensors operate in STATE 0.
Note sensor STATES are not applicable for wireless sensors.

S-Cubed Mark 2 (Legacy product range)

The Sounders in the following S-Cubed Mark 2 range of products listed below are LPCB approved to EN 54 : Part 3
S3IP-VP-W, S3-VP-W, S3IP-VP-ST-WR, S3-VP-ST-WR, S3IP-VP-R, S3-VP-R, S3IP-VP-ST-RR, S3-VP-ST-RR, S2IP-VP-W, S2IP-VP-R, S3IP-SN-W-V2, S3-SN-W-V2, S3IP-SN-ST-WR-V2,
S3-SN-ST-WR-V2, S3IP-SN-R-V2, S3-SN-R-V2, S3IP-SN-ST-RR-V2, S3-SN-ST-RR-V2, S3IP-SN-ST-RW-V2, S2IP-SN-R-V2 and S2IP-SN-W-V2.
16
LPCB approved STATE
# - default STATE
STATE 0 #
S4-711-ST
(With Strobe)
S4-711-VO
S4-711-ST-VO
STATE 5
S4-771
STATE 8
STATE 0 #
S4-911
S4-911-ST-VO
STATE 9
S4-770 STATE 0 #
STATE 0 #
S4-720-ST-VO
S4-780
S4-780-ST
(With Strobe)
STATE 5
Meets ~ EN54 : Part 7 :2000
* EN54 : Part 5 :2002
Medium optical smoke ~ / Class A1 heat *
Medium optical smoke ~ / Class B heat *
Delayed medium optical smoke ~ / Class A1 heat*
Medium optical smoke ~ / Class A1 heat *
Class A1 heat *
Medium optical smoke / Class A1 heat*
Class A1 heat *
Class B heat *
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.