How To Configure The Monitored Input - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

PSU EEPROM link
Ensure a shorting link is fitted to the programming header P1 located on the PSU. The link must be
fitted such that it shorts pins 1 and 2. This enables the EEPROM hardware write protect.
"
The link is supplied fitted on the PSU board manufactured after September 2007.
Ensure a link
is fitted accross
pins 1-2
P1
P3
43V
FS6
1A P7
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
PSU BOARD
(part view)
Y1 Y2 G1
BAT1
-
+
Vigilon 4/6 loops & Compact (VA) panels & network nodes

How to configure the monitored input

Normally open contacts
These contacts can be a push button
switch, fire/fault relay contacts from
another panel or contacts from a timer.
2 - 10K Ohms -
resistors must be
fitted as shown.
0V MIP
An active input will trigger
P8
the command build No 250
Monitored Input
The command build action
is configured during commissioning.
MASTER CONTROL
BOARD
PANEL
The monitored input at the fire panel is activated by an external switch installed a maximum of
100m cable distance away from the fire panel. The input is monitored for both short and open
circuit faults. When the input is active it triggers the command build number 250 of the fire panel.
Example
The following example shows how to configure the monitored input at the panel to provide an
output sound signal 1 alarm in sector 2 of loop 1 as a reversible action. This means on operating or
"closing" the monitored input the panel will start alarms in sector 1 and on releasing or "opening"
the monitored input the panel will stop all the alarms from sounding.
# - will appear if a PIN is setup.
The following procedures assume a password entry is not required.
Press Menu On/Off button and select [SetUp] -> [Usercode]#, momentarily press <etc> to select
[SetUp] -> [Build] and type in the command build number 250, select [Action] -> [UserCode],
momentarily press <etc> to select [Sector], type in 2 for sector 2 and select [Loop] and type in 1
for Loop 1 -> [Action] -> [Signal 1] -> [Enter] -> [reversb] -> [Enter].
41