Domain Bridge Message Passing Tests; Domain Bridge Using Fibre Optic Network Card - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions

Domain bridge message passing tests

To check the domain bridge connections and to ensure messages
can be passed between networks the following must be done.
Trigger an event in a network, such as a fault.
¨
Check the event is passed on to the connecting networks
and is displayed at the networked control panels
¨
Repeat the test at each network to establish message
passing between networks
¨
Finally back up the cards of the panel including the
Network card and IO card to the Memory. This ensures
the panels of each network knows the location of
network controller, ie the domain bridge connection
point.
96

Domain bridge using Fibre Optic network card

Up to 64 small VIGILON networks can be connected together in a secure loop by using domain bridge fibre optics network card
(VIG-NC-DOM-FO), with the card installed in socket P7 of the backplane. This allows the display of events at any control panel in
the connected networks.
Zones
1
17
2
18
19
3
20
4
21
5
23
22
6
24
8
7
9
25
26
10
27
11
12
28
13
29
30
14
15
30
16
32
Fault
Fire
Network
Power Fault
15:45
Verify
System Fault
Vigilon Fire System
GENT 20XX
Sounder
Delay
Designed to EN54 Pt 2 & 4
Cb253
Disablement
Test
Previous
Next
CB254
Power
domain bridge
Zones
1
2
3
4
5
6
7
9
8
10
11
17
18
19
20
21
22
23
24
25
26
27
Fault
Power Fault
System Fault
Vigilon Fire System
Delay
Designed to EN54 Pt 2 & 4
GENT 20XX
Test
Previous
Next
Disablement
Zones
1
17
2
18
3
19
20
4
21
5
22
23
6
7
24
8
25
9
10
26
27
11
13
28
12
30
29
14
15
30
16
32
#
Fault
Fire
Power Fault
15:45
Verify
System Fault
Vigilon Fire System
GENT 20XX
Sounder
Delay
Designed to EN54 Pt 2 & 4
Cb253
Disablement
Test
Previous
Next
CB254
Power
#
Zones
1
17
18
19
2
3
20
4
21
5
22
6
23
7
8
24
9
25
26
27
10
11
12
28
13
29
30
14
30
15
16
32
Fault
Fire
Power Fault
15:45
Verify
System Fault
Vigilon Fire System
GENT 20XX
Sounder
Delay
Designed to EN54 Pt 2 & 4
Cb253
Disablement
Test
Previous
Next
Power
CB254
Zones
18
1
17
2
19
3
20
4
5
21
6
22
23
7
8
24
25
10
9
26
11
27
28
12
13
29
14
30
30
15
32
16
Power Fault
Fault
15:45
Verify
Fire
System Fault
Vigilon Fire System
GENT 20XX
Sounder
Delay
Designed to EN54 Pt 2 & 4
Cb253
Disablement
Test
Previous
Next
Power
CB254
#
Zones
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
30
32
Fault
15:45
Fire
Power Fault
System Fault
Vigilon Fire System
Sounder
Verify
Delay
Designed to EN54 Pt 2 & 4
GENT 20XX
Cb253
Test
Previous
Next
CB254
Disablement
Power
Zones
17
1
18
2
20
19
3
4
21
5
22
6
23
7
24
8
25
9
10
26
27
11
12
28
Fault
Power Fault
System Fault
Vigilon Fire System
Delay
Designed to EN54 Pt 2 & 4
GENT 20XX
Disablement
Test
Previous
Next
#
Zones
17
2
1
18
3
19
4
20
5
21
22
6
7
23
25
8
24
26
9
10
27
11
12
28
13
29
30
14
15
30
32
16
Fault
Fire
Power Fault
15:45
Verify
System Fault
Vigilon Fire System
GENT 20XX
Sounder
Delay
Designed to EN54 Pt 2 & 4
Cb253
Test
Disablement
Previous
Next
Power
CB254
#
Zones
17
1
18
2
19
20
3
21
4
5
6
22
7
23
24
8
9
25
26
10
28
12
27
11
Fault
Power Fault
System Fault
Vigilon Fire System
GENT 2004
Delay
Designed to EN54 Pt 2 & 4
Zones
18
17
1
2
19
3
4
20
21
5
6
22
23
7
25
24
8
9
10
26
11
27
28
12
29
13
30
14
30
15
32
16
Test
Disablement
Previous
Next
Fault
Fire
Power Fault
15:45
Verify
System Fault
Vigilon Fire System
GENT 20XX
Sounder
Delay
Designed to EN54 Pt 2 & 4
Cb253
Test
Disablement
Previous
Next
CB254
Power
#
The above diagram shows small fibre networks connected together by a fibre network domain. It is equally possible to mix small
copper networks and small fibre networks together in the manner shown above to a network domain.
Zones
17
1
18
2
19
3
20
4
21
5
6
22
7
23
24
25
8
9
26
10
27
11
12
28
29
13
30
14
30
15
32
16
Fault
Fire
Power Fault
15:45
Verify
System Fault
Vigilon Fire System
GENT 20XX
Sounder
Delay
Designed to EN54 Pt 2 & 4
Cb253
Disablement
Test
Previous
Next
Power
CB254
#
Fibre Optics Domain bridge network card
(
VIG-DOM-NC-FO)
12
13
14
16
15
28
29
30
30
32
15:45
Fire
Sounder
Verify
Cb253
CB254
Power
Fibre optic
Panel/Node
patch panel
1
2
3
4
5
6
7
8
10
9
11
12
13
14
15
16
Zones
17
18
19
20
21
22
23
24
25
26
27
28
29
30
30
32
Fault
15:45
Fire
Power Fault
Verify
System Fault
Delay
Designed to EN54 Pt 2 & 4
Vigilon Fire System
GENT 20XX
Sounder
Cb253
Test
CB254
Disablement
Previous
Next
Power
Tx
Rx
Zones
18
17
1
19
3
2
20
4
21
5
6
22
23
7
8
24
9
10
25
26
11
27
28
12
13
29
30
14
15
30
32
16
Fault
Fire
Power Fault
15:45
Verify
System Fault
Vigilon Fire System
GENT 20XX
Sounder
Test
Delay
Designed to EN54 Pt 2 & 4
Cb253
CB254
Disablement
Previous
Next
Power
29
13
30
14
30
15
16
32
15:45
Fire
Verify
Sounder
Cb253
CB254
Power
Zones
1
3
2
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
30
32
Fault
15:45
Fire
Power Fault
Vigilon Fire System
Sounder
Verify
Delay
System Fault
Designed to EN54 Pt 2 & 4
GENT 20XX
Cb253
Test
CB254
Disablement
Previous
Next
Power
29
13
14
30
15
30
32
16
15:45
Fire
Verify
Sounder
CB253
CB254
Power
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
installed in P7 of backplane
Fibre optic
Panel/Node
patch panel
Tx
Rx
Fibre patch cable

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vigilon 6 loopVigilon compactVigilon compact va

Table of Contents