S-Quad Heat sensor STATES

# - factory default STATE
State
Definition / Class
State 0# Class A1 heat
State 13 Class A2 heat
State 5
High temperature Class B heat
State 6
High temperature Class BS heat - with
no rate of rise component
State 15 No detection
S-Quad Dual Optical & Heat / Optical & Heat sensor STATES
# - factory default STATE
State
Definition / Class
State 3
High sensitivity optical,
Class A1 heat
State 4
Medium sensitivity with no optical spike
protection, Class A1 heat
State 0# Medium sensitivity optical, Class A1
heat
State 8
Delayed medium sensitivity optical,
Class A1 heat
State 5
Medium sensitivity optical, Class B heat Area having high ambient temperature with low dust, smoke or steam present
State 2
Low sensitivity optical, Class A1 heat
State 11 Low sensitivity optical,
Class B heat
State 6
Low sensitivity optical,
Class BS heat
State 12 Class A1 heat only
State 15 No detection
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Application in / Suitable for:
Area having high levels of smoke, dust or steam
Area where there is moderate temperature changes plus dust, smoke or steam present
Area having high ambient temperature plus dust, smoke or steam present
Area where there is rapid temperature changes plus dust, smoke or steam present
Application in / Suitable for:
Clean area or environment, where early detection is required
General area as State 0 with less immunity to steam and dust to facilitate witness test
General area
General application in area with transient steam, dust or smoke present
Areas with moderate dust, smoke or heat during working hours when used with timing function
Area having high ambient temperature, plus where moderate dust, smoke or steam present
Area having high ambient temperature that changes, plus moderate dust, smoke or steam
present
Area where smoke, dust or steam occurs at times
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Sensitivity
a-high- to-e-none
a
b
c
d
e
Sensitivity
a-high- to--j-none
a
b
c
d
e
f
g
h
I
j